background image

2684

6

GB

4.

WORKING

4.1 COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and
testing must be carried out observing the instruction manual of the boiler, including verification of the CO and
CO

2

 concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.

To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the setting of
the combustion head, and the air damper opening in accordance with the following table.

ADJUSTMENTS FOR SIME BOILERS

The values shown in the table are measured on a SIME boiler (as per EN 267).
They refer to 12.5% CO2 at sea level and with light oil and room temperature of 20 °C.   

Burner adjustments carried out in factory. 
In case of matching with a boiler different from the “Rondò-Estelle 6” model, for the adjustments fol-
low what indicated in the table.

APPROXIMATE ADJUSTMENTS FOR INSTALLATION ON OTHER BOILERS

The values shown in the table are measured on a CEN boiler (as per EN 267).
They rfer to 12.5% CO2 at sea level and with light oil and room temperature of 20 °C.

4.2 NOZZLES RECOMMENDED:

Monarch type R

;  

Delavan type W - B

Steinen type S - Q ;

Danfoss type S - B

For 2.00 – 250 GPH nozzle it is advisable to use, if possible, 
full cones.

BOILER

BURNER - Code 8099050 - Model MACK 6

Nozzle

Pump

pressure

Burner

output

Combustion

head adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h 

±

 4%

Set-point

Set-point

Rondò-Estelle 6 

1.10

60° W

12

4.4

2.0

3.0

Rondò-Estelle 7

1.25

60° W

13

5.2

2.5

3.5

1R 6

1.50

60° B

12

6.0

3.0

3.5

1R 7

1.75

60° B

12

7.0

3.5

4.0

1R 8

1.75

60° B

14

7.6

4.0

5.0

Nozzle

Pump

pressure

Burner 

output

Combustion 

head adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h ± 4%

Set-point

Set-point

0.85

60°

12

3.4

1

2.1

1.00

60°

12

4.0

1.5

3.2

1.10

60°

12

4.4

2

3

1.25

60°

12

5.0

2

3.4

1.50

60°

12

6.0

3

3.4

1.75

60°

12

7.0

4

4.5

2.00

60°

12

8.0

5

5.2

2.25

60°

12

9.0

6

5.5

2.25

60°

14

9.8

6

6

2.50

60°

12

10.0

6

8

Summary of Contents for 8099050

Page 1: ...gebruiks en onderhoudsvoorschriften Installation use and maintenance instructions Oil burner Br leur fioul Stookoliebrander CODE MODEL MODELE TYPE 8099050 SIME MACK 6 412 T GB F NL One stage operation...

Page 2: ...n adjustment 6 4 2 Nozzles recomended 6 4 3 Maintenance position 7 4 4 Electrode setting 7 4 5 Combustion head setting 7 4 6 Air damper adjustment 8 4 7 Pump pressure 8 4 8 Burner start up cycle 9 4 9...

Page 3: ...ingle phase 50Hz 230V 10 Motor Run current 0 80A 2850 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 7 15 bar Absorbed electrical power 0 17 kW Flange Burner 326 1...

Page 4: ...lange 1 the screw and two nuts see fig 2 Widen if necessary the insulating gasket holes 5 Fix the flange 1 to the boiler door 4 using screws 2 and if necessary the nuts 3 interposing the insulating ga...

Page 5: ...a non return valve is required This solution however is less safe than previous one due to the possibility of leakage of the valve It is necessary to install a filter on the fuel supply line The stan...

Page 6: ...he Country DO NOT EXCHANGE NEUTRAL WITH PHASE WARNING ACCESS TO THE PHOTORESISTANCE See fig 9 The photoresistance is fitted directly into the con trol box underneath the ignition transformer on a plug...

Page 7: ...stments fol low what indicated in the table APPROXIMATE ADJUSTMENTS FOR INSTALLATION ON OTHER BOILERS The values shown in the table are measured on a CEN boiler as per EN 267 They rfer to 12 5 CO2 at...

Page 8: ...l the terminal plane of the blast tube is level with the set point as indicated in the schedule In the sketch on fig 12 the combustion head is set for an output of 1 50 GPH at 12 bar while the shutter...

Page 9: ...ed screw tight the screws 4 to assure a free movement of the mobile air damper 1 The settings indicated in the table at page 6 refer to the burner with its cover fitted and combustion chamber with dep...

Page 10: ...d authorized technicians Maintenance is essential for the reliability of the burner avoiding the excessive consumption of fuel and consequent pollution Before carrying out any cleaning or control alwa...

Page 11: ...fied personnel FAULTS POSSIBLE CAUSES SOLUTION The green led on the control box is off and the burner does not start Lack of electrical supply Check presence of voltage in the L1 N clamps of the 7 pin...

Page 12: ...Fonderie Sime S p A via Garbo 27 37045 Legnago Vr Italy Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime Service fax number 39 0442 631292...

Reviews: