ALARM TRANSMISSION TEST
Shorting and disconnecting of SIM2W-FLOOD-I
sensor contacts pins unit enables the alarm
transmission test feature.
Check that the transceiver unit indicates at least 2
events
– one for shorting and one for
disconnecting the SIM2W-FLOOD-I
sensor
contacts.
To check this function it is necessary to verify that
the control panel displays the following message:
TESTING THE DETECTOR
Walk Test
A. Set the control panel to "Walk Test Mode" as described
in the Installer Manual. B. Make a momentary short
between the two golden contacts pins of the sensor C. the
alarm should appear on the control panel display.
Tamper Transmission Test
Pressing and releasing the tamper (push button) enables
the TAMPER transmission test feature.
Verify the Control Panel indicates "Zone Tamper open"
and TROUBLE LED is ON.
Close the Tamper and verify the Control Panel Indicates
ZONE TAMPER OPEN is restored and TROUBLE LED is
OFF.
In some control panels READY LED will turn OFF when
tamper is open and ON when closed.
Transmission can also be reviewed on the transceiver unit
as a rapid Red-Green-LED blink.
BATTERY REPLACEMENT
Remove the front cover.
Pull out the old battery.
Install a new battery according to polarity marking.
After assembling the battery the LED will flash
Green then Red alternately for 45 seconds.
During this time the detector does not function,
wait until the LED stop flashing.
Press tamper for 2 sec and then release it.
Note:
LED indications
Green/Red LED flashes 6 times alternately:
The detector was successfully registered in system.
The cover may be placed back and closed.
Green LED blinks 20 times:
No response from Transceiver / device was not
assigned on CP - Repeat installation procedure.
Red LED blinks continually (over 20 sec):
Battery voltage is critical low device won't
function - Replace battery.
16
17
18
TECHNICAL SPECIFICATIONS
Data Protocol
Two Way Wireless
Frequency
868.35MHz
Identification
Unique ID serial number
– 24 bit
Event Transmission
Alarm, Tamper,
Supervision, Low Bat,
Supervision
Detection Method
External golden
contacts pins device
Range in open space
500m
Battery
Lithium. 3V Type:
CR123A Size: 2/3AA
Battery life
>5 years
( 10 activation per day)
Current Consumptions
Standby ~3
A
Receive mode ~29 mA
Transmit mode~38 mA
Low Battery
~2.4Vdc
Transmit power
~10dBm
Tamper Switch
Front Cover Removal;
Back Tamper
Operating temperature
10
C to +50
C
Dimensions
97mm x 22mm x 21mm
Weight (inc. battery)
40 gr.
CAUTION !!!
RISK OF EXPLOSION IF BATTERY IS REPLACED BY DIFFERENT TYPE / MODEL.
DISPOSE USED BATTERIES ACCORDING TO ITS INSTRUCTIONS
19
Zone # X Open
The battery must be replaced
by 3V
Lithium battery Size 2/3A
Models such as:
1. VARTA CR123A
2. GP CR123A