INS377 MESH-HBSP (Issue 03)
MESH-HBSP
Ceiling High Bay (Spot) Passive Infra Red
(PIR) Occupancy Detector & Photocell
Input: 100-240 Vac 50/60Hz
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
NOTE: MESH-
HBSP
is compatible with any qualifi ed Bluetooth mesh components and commissioning tools.
We recommend Silvair Commissioning as a reliable solution.
HALL EFFECT / FACTORY RESET:
This function allows a reset to be carried out in order to restore the default
factory settings.
A factory reset will change the state of MESH-HBSP from ‘provisioned’
to ‘unprovisioned’, i.e. all network settings will be lost. This functionality is
required to allow reprovisioning MESH-HBSP where control over the device
is not functioning correctly.
TO REPROVISION:
Place a small magnet on the site of the Reset / Hall effect sensor (see
diagram 4 below). To trigger the reset the magnet must be held in position
for 5 seconds.
DIMENSIONS
RESET ZONE
(behind moulding). Magnet
to be placed over the Reset
Sticker for reprovisioning.
STATUS LED.
Flashes rapidly when
unprovisioned. Flashes
slowly when provisioned.
DIAGRAM 4
STATUS LED BLINKING SEQUENCE:
MESH-HBSP Unprovisioned:
30ms ON
300ms OFF
MESH-HBSP Provisioned:
15ms ON
2000ms OFF
Factory Reset:
500ms ON
1000ms OFF
Factory Reset (initial burst):
100ms ON
1000ms OFF
MESH package received:
30ms ON
50ms OFF
Attention (from network):
500ms ON
500ms OFF
DIAGRAM 3
plan
side
63
90
90
76