52
007-6399-002
4: Rack Information
E-Cell Cooling Rack Specifications
There is one dedicated cooling rack for every two E-racks in an E-Cell assembly. The cooling rack
circulates conditioned air through the E-racks to cool the components within the E-rack assembly.
Figure 4-3 on page 50 shows the cooling rack at the center of the array. Note that the cooling rack
does
not
house any compute or storage components and is strictly for cooling the E-Cell assembly.
Table 4-3 lists the major characteristics and specifications of the E-Cell cooling rack.
Table 4-3
SGI ICE XA E-Cell Cooling-Rack Specifications
Characteristic
Specification
Cooling rack height
93 in. (236.2 cm)
E-Cell cooling rack width
23.6 in. (60 cm)
E-Cell cooling rack depth
60 in. (152.4 cm)
Shipping height/width/depth
89.5 in. (228 cm) x 38.6 in. (98 cm) x 63 in. (160 cm) [pallet & crate]
Cooling rack weight (unit)
Shipping weight (max)
Approx. 1,400 lbs. (635 kg)
Approx. 1,816 lbs. (825.5 kg)
Voltage range
Nominal
Tolerance range
North America & Japan/International
480 VAC ___________/400 VAC
456-504 VAC _______/312-457 VAC
Frequency
Nominal
Tolerance range
North America/International
60 Hz / 50 Hz
47-63 Hz / 47-63
Phase required
3-phase
Power requirements (max)
10 kVA / 9.2 kW
Power cable
8 ft. (2.4 m) pluggable cords
Hold time
16 ms
Hold time
16 ms
Power cable
8 ft. (2.4 m) pluggable cords
Table 4-2
SGI ICE XA E-Rack Technical Specifications
(continued)
Characteristic
Specification
Summary of Contents for ICE XA
Page 1: ...SGI ICE XA System Hardware User Guide Document Number 007 6399 002 ...
Page 4: ......
Page 12: ......
Page 25: ...Powering the System On and Off 007 6399 002 7 Figure 1 4 Three Phase PDU Example ...
Page 32: ......
Page 65: ...SGI ICE XA Series D Rack 42U 007 6399 002 47 Figure 4 1 D Rack Front Lock Example ...
Page 72: ...54 007 6399 002 4 Rack Information Figure 4 4 E Cell Rack Assembly Example CDU on Left ...
Page 82: ......