![SILENT KNIGHT 5495 Installation And Operation Manual Download Page 8](http://html.mh-extra.com/html/silent-knight/5495/5495_installation-and-operation-manual_1271130008.webp)
151161
3-4
You can select which input controls which output, and which inputs are Class A and Class B using the 7-position
DIP switch on the printed circuit board. Section 4.8 for DIP switch settings.
2
Input 1 or
Outputs 1, 2, 3, and 4
Class B ANSI temporal-
Input 2
coded circuits
3
Input 1
Outputs 1 and 2
Class B circuits
Input 2
Outputs 3 and 4
Class B circuits
4
Input 1
Output 1
Class B circuits
Input 2
Outputs 2, 3, and 4
Class B circuits
5
Input 1
Outputs 1-2 and 3-4
Class A circuit pairs
6
Input 1
Outputs 1 and 2
Class B ANSI temporal-coded circuits
Input 2
Outputs 3 and 4
Class B circuits
7
Input 1
Outputs 1-2
Class A circuit pair
Input 2
Outputs 3-4
Class A circuit pair
8
Input 1
Outputs 1-2
Class A circuit pair
Input 2
Outputs 3 and 4
Class B circuits
9
Input 1 (Strobe Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
Faraday Sync. Output
10
Input 1 (Strobe Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
Gentex Sync. Output
11
Input 1 (Strobe Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
System Sensor Sync. Output
12
Input 1 (Strobe Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
Wheelock Sync. Output
13
Input 1 (Strobe Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
Amseco Sync. Output
For Option:
These Inputs:
Control These Outputs:
As: