Model 5495 Distributed Power Module Installation Manual
4-9
4.4
Connecting the 5495 to a Control Panel
Figure 4-2 shows the general layout of the 5495 PC board. This section also provides specific wiring details for
accessories.
Figure 4-2 The Model 5495 PC Board Layout
Consult the installation manual for specific wiring information for the control panel being used.
4.4.1
Common Trouble Relay
The 5495 has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open and a
normally closed contact, both of which are rated at 2.5A. The trouble relay will deactivate under any trouble
condition.
A typical application of the trouble relay is to connect the 5495 normally closed (N.C.) contacts in series with the
EOL supplied with the fire alarm control panel. This will cause a trouble on the fire alarm control panel when the
5495 opens its trouble contacts.