30
16.2 Silent Knight FSK and 4+2 Formats
The Silent Knight FSK and 4+2 formats transmit a 4-digit account number and a 2-digit alarm code. When an
event is reported in either of these two formats, the dialer transmits the two digits shown in the second column.
The 9000 can be programmed to print either the two digits or the English message shown in the third column of
Table 16.2-I. If you are using the 9032 line card, FSK2 and BFSK are the only formats that will report in
English.
Table 16.2-I: 9000 Pringout for Silent Knight FSK and 4+2 Formats
5128/29
DIGITS
TRANSMITTED
9000 RECEIVER ENGLISH
LANGUAGE PRINTOUT
ALARM 1-4
**01-04
ALARM 01 - ALARM 04
ALARM RESTORE 1-4
**21-24
RESTORE 01 - RESTORE 04
TROUBLE 1-4
61-64
TROUBLE 01 - TROUBLE 04
TROUBLE RESTORE 1-4
71-74
AC TROUBLE
AC LOST
60
AC RESTORE
AC RESTORE
70
TEST
MANUAL TEST
30
TEST
AUTOMATIC TEST
30
TEST
FIRE DRILL
30
TEST
*DOWNLOADING SUCCEEDED
30
TEST
*DOWNLOADING FAILED
30
TEST
PHONE LINE #1 TROUBLE
31
PHONE LINE TROUBLE 01
PHONE LINE #2 TROUBLE
32
PHONE LINE TROUBLE 02
DATA LOST
39
DATA LOST
PHONE LINE #1 RESTORE
35
PHONE LINE RESTORE 01
PHONE LINE #2 RESTORE
36
PHONE LINE RESTORE 02
*Message not applicable.
**“02” and “22” will never be reported. Channel/Zone 2 is a trouble indication only that will transmit
only “62” and “72.”