![Silent Alert SA3000 Technical Manual Download Page 4](http://html.mh-extra.com/html/silent-alert/sa3000/sa3000_technical-manual_1271002004.webp)
SILENT ALERT SA3000 FIRE SAFE MANUAL 24/04/2015
Designed & Manufactured by Clofield Limited
Free technical helpline 01246 450789 www.silent-alert.co.uk
Alarm Output from main fire alarm panel
It is possible to trigger the unit by the removal of an external voltage using the bottom I/O
terminal.
The Interface Panel requires an external voltage of at least 5
– 30V AC
or DC.
NOTE
the maximum voltage must not exceed 30v AC or DC or damage
will occur to the panel invalidating warranty.
Fault conditions from Fire Safe panel
The Fire Safe panel has a fault output to the main fire alarm panel
provided via the top terminal block. A fault condition on the Fire Safe
panel will cause a relay to be closed that will create an open circuit
between common and normally closed (N/C) and a closed circuit
between normally open (N/O) and common.
A fault alarm will be given in the following conditions:
Mains failure
Battery charge failure or removal
Loss of radio signal
Main PCB failure
Front Panel Indicator Lights
Mains
Green
Lit when mains power present
Battery
Green
Lit when battery present
Charging
Yellow
Lit whilst battery is charging
Fault
Orange
Lit when any of the above fault conditions occur
Poll
Yellow
Lit constantly, goes out when poll signal is sent
Alarm
Red
Lit when alarm signal received from fire panel
Disable
Orange
Lit when disable key is turned to the on position
Test
Red
Lit when in range test mode.
GND
N/C
N/O
COM