Siko MBA1000 User Information Download Page 11

MBA1000 

      Datum 26.08.2008 

Art.Nr. 79828 

Änd. Stand 318/08 

11

5.3 Sensor's SSI-interface

MSA1000's SSI-interface allows a synchronuous out-
put of the position value. Its data format comprises 
a width of 24 bit which are either issued as Gray or 
binary codes (see chapter 7) and right-aligned. All 
following bits  (25, 26...) are issued as "0".
Data signals correspond to RS422. Cycle inputs are 
opto-decoupled and also correspond to RS422. Ty-
pical SSI monoflop time is . 20...25µs which gives 
a min. cycle rate of 62,5kHz.
Please note that the possible max. cycle rate and 
data integrity mainly depend on the length of the 
connection line. The following standard values can 
be given:
line length 2m 

max. cycle rate: 

1 MHz

line length 10m 

max. cycle rate: 

800 kHz

line length 100m 

max. cycle rate: 

250 kHz

line length 200m  

max. cycle rate: 

125 kHz

5.4 Sensor in bus operation

Two  different  protocols  are  implemented  in  the 
MSA1000 firmware.
The  differentiation  between  the  "service  mode" 
and the "SIKONETZ3" protocol is effected via the 
wiring of the configuration input on "pin L" of the 
connector.
After switching on, the RS485 interface is set to 
"service mode" as long as the configuration input 
"pin L" is not wired. The device address required 
for  subsequent  bus  operation  (SIKONETZ  3)  can 
only  be  changed  in  this  mode  (default  address 
01). After switching on the sensor, the program-
ming  tool  "demo1000.exe"  must  be  started  and 
the displayed sensor paraqmeters be checked. The 
software version should be 1.01 or better. Using 
function  key  "F5",  the  sensor  address  (01...31) 
can  be  entered  and  shown  in  the  window  that 
is  dis-played.  The  address  is  then  automatically 
stored  in  the  sensor  and  is  retained  after  swit-
ching off the power supply. 
The  configuration  input  "pin  L"  must  be  put  to 
GND whenever the sensor is used during bus ope-
ration. The input is queried during startup, and in 
this case the RS485 protocol is set to SIKONETZ3.

6.  Trouble shooting

Below there are some typical errors which may oc-
cur during installation and operation:

Sensor  not  or  incorrectly  connected  (for  pin 
connection see chapter 4).
Tolerance for the gap between magnetic sensor and 
magnetic strip not observed over the  total  travel 

distance. Sensor touches strip (see chapter 7).
Cable  squeezed  /  interrupted  /  cut  by  sharp 
edges.
Sensor’s  active  side  not  mounted  towards  the 
magnetic strip (see fig. 8).
Sensor  and magnetic strip have been incorrectly 
aligned (see chapter 1).
Magnetic fields near the measuring surface distort 
the measuring values. If required, pro-vide for 
adequate screening.
Wrong measuring values due to EMC interferences 
(see chapter 4).

7.  List of commands / service mode

Parameters:  19200 Baud, no parity, 8 bit, 1 stop 

bit, no handshake

Data code:  ASCII / Hexadecimal
Value range: 2/3 Byte: 0...65535 / 0...± 2

23

All  replies  which  are  confirmed  by  ">"  end  with 
"CR" (Dez 13)."

Com.

Length Reply

Description

Ax

Send unit type/software version

2/9 "xxxxxxx>" x=0: hardware version

2/10 "xxxxxxxx>" x=1: software version

B

1/10 "±xxxxxxx>" Send absolute value (without cor-

rection values)

Ey

2/10 "±xxxxxxx>" Issue a 3-byte value

y=address (0...4)
y=1:position value
y=2:zero position value
y=3:calibration value
y=4:offset value
±xxxxxxx=dec. value

Fy±xxxxxx

9/2 ">"

Enter 3-Byte value
y=address (2...4) 
y=2:zero position value (default=0)
y=3:calibration value (default=0)
y=4:offset value (default=0)
±xxxxxxx=dec. value

K

1/0 ""

Software reset

L

1/2 ">"

zero position value (calibration)

Nx

2/2 ">"

enter SSI output code
x=0: Gray code (default)
x=1: binary code

Qxx

3/2 ">"

enter  device  address  (for  SIKO-
NETZ 3 protocol)
xx= 01...31

R

1/4 "xx>"

output device address
xx= address

Sxxxxx

6/2 ">"

restore  default  programming
x= 11100 (s_befehl)
zero  point/calibration/offset  va-
lue =0
count. direct.= positive
output code= Gray
device address = 01

Tx

2/2 ">"

enter counting direction
x=0: positive count. direction (default)
x=1: negative count. dirction

Summary of Contents for MBA1000

Page 1: ...ion MSA1000 MBA1000 Magnetsensor und Magnetband 3 1 Montage Magnetband Die Montage muss plan zur Montage che bzw der zu messenden Strecke erfolgen Welligkeiten verschlechtern immer die Messgenauigkeit...

Page 2: ...olchen F llen sind Montagearten wie in Abb 4 und 5 gezeigt geeigneter Den optimalen Schutz bietet die Montage in einer Nut Abb 6 die so tief sein sollte dass das Magnet band vollst ndig darin eingebet...

Page 3: ...zlicheMa nahmen wie Schirmbleche oder metallisierte Geh use vorzusehen Leitungsf hrungen parallel zu Ener gieleitungen sind zu vermeiden Sch tzspulen m ssen mit Funkenl schgliedern beschaltet sein Spa...

Page 4: ...es notwendig sein sollte ist kein Ableich notwendig 5 1 Programmierung des Sensors Der MSA1000 kann ber die integrierte RS485 Schnittstelle an die Bed rfnisse angepasst wer den Hierf r haben Sie die M...

Page 5: ...pbit ohne Handshake Ausgabe ASCII Hexadezimal Wertebereiche 2 3 Byte 0 65535 0 223 Alle Ausgaben die eine Best tigung beinhalten werden mit einem CR Dez 13 abgeschlossen Befehl L nge Antwort Beschreib...

Page 6: ...rtebereiche 2 3 Byte 0 65535 0 223 Im SIKONETZ3 Protokoll sind zwei feste Tele gramml ngen m glich 3 oder 6 Byte Der Aufbau gliedert sich in Adressbyte Befehlsbyte Datenlowbyte nur bei 6Byte L nge Dat...

Page 7: ...ormation MSA1000 MBA1000 Mangetic sensor and strip 3 1 Mounting the magnetic strip The mounting surface measuring track must be at Buckles or bumps will lead to inaccurate measurement results Please p...

Page 8: ...l There we recommend mounting accord to g 4 and g 5 Mounting in a groove g 6 best protects the magnetic strip The groove should be deep enough to totally embed the magnetic strip 3 2 Sensor mounting W...

Page 9: ...ded The running of wiring parallel to the mains supply should be avoided Contactor coils must be linked with spark sup pression Power supply 24 VDC 20 20 Power consumption 10VA 4 1 Connection type E3...

Page 10: ...nufacturer Even if the magnetic strip is ex changed later a re alignment is not necessary 5 1 Sensor programming Certain parameters of sensor MSA1000 are program mable via its RS485 interface and are...

Page 11: ...us ope ration The input is queried during startup and in this case the RS485 protocol is set to SIKONETZ3 6 Trouble shooting Below there are some typical errors which may oc cur during installation an...

Page 12: ...length Data middle byte only with 6 bytes length Data high byte only with 6 bytes length Checksum EXOR of the preceding bytes of this telegram Setup of the address byte 0 1 2 3 4 5 startbit A0 A1 A2...

Reviews: