background image

LED Architectural  Emergency Light

Universal 120/ 277 VAC Supply

1. Disconnect AC power before servicing.

7. Mount and secure the fixture at a location and height  to avoid ready access  

2. Refer to wiring diagram for proper connections.

and tampering by unauthorized persons.

3. All servicing should be performed by qualified personnel.

8. The use of accessory equipment is not recommended by the manufacturer 

4. Consult your local building code for approved wiring and  installation.

and may cause an unsafe condition.

5. Do not use this equipment for other than intended use.

9. Suitable for wet locations. See product label for temperature limitations.

6. Do not let power cords touch hot surfaces.

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

Series MAE-AC

MoonLite LED

INSTALLATION INSTRUCTIONS AND OWNER'S MANUAL

SUITABLE FOR WET LOCATIONS

AMBIENT TEMPERATURE LIMITS:

Standard models: -20º C to +40º C

Remote models: -40º C to +50º C

J- Box and Supply Wiring

1. See above for available K.O.'s for wiring connectors. Select K.O.'s for AC input wiring. Install standard 
4” x 4” deep j-box with 1 ½” extension.

 IMPORTANT:

  SET J-BOX ASSEMBLY TO ALIGN EDGE OF EXTENSION FLUSH OR JUST BELOW 

FINISH PANEL SURFACE.

2. See above. Insert Power Supply Assembly (1) into j-box and secure with two #8-32 x ½” screws.  

3. See above. Connect  AC input wiring from power supply assembly to building supply with wire nuts, 

 05.10.01

1

(2) # 8-32 x 1/2
J-BOX MOUNT 
SCREWS

LAMP PLUG

GROUND
TO J-BOX

L N G

120/277 VAC

B

W

EXTENSION

RING 1 1/2"

J-BOX

4 x 4 x 2 1/8"

AVAILABLE K.O.'S
4 PLACES

SET EDGE OF BOX
FLUSH TO WALL 
FINISH OR
PANEL THICKNESS

STANDARD J-BOX
4 x 4 x 21/8"

EXTENSION  RING
4 x 4 x 11/2"