background image

page 3 of 8

‡ SIGNET

 8550-1 Flow Transmitter

3.1 System Power/Loop Connections

3.2 Sensor Input Connections

Wiring Tips:

Do not route sensor cable in conduit containing AC power wiring. Electrical noise may interfere with sensor signal.

Routing sensor cable in grounded metal conduit will help prevent electrical noise and mechanical damage.

Seal cable entry points to prevent moisture damage.

Only one wire should be inserted into a terminal. Splice double wires outside the terminal.

Transmitter

≤ 200 ft. (61 m)

Transmitter

≤ 1000 ft. (300 m)

Maximum cable length is 200 ft. for 515/8510-XX, 525 , 2517 and
any sinusoidal flow signal.

Maximum cable length is 1000 ft. for 2536/8512-XX, 2540, vortex,
and any square wave flow signal.

Stand-alone application, no current loop used

Transmitter

           Terminals

4
3
2
1

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Power Supply
DC 12 - 24 V

Power
Supply
Power
Supply

Connection to a PLC with built-in power supply

PLC

Terminals

Power Supply
Ground
Power
Supply
Loop Input
4-20 mA
Loop Input
4-20 mA 

Internal PLC
Connection

Connection to a PLC/Recorder, separate supply

PLC or Recorder

Loop Input
4-20 mA in
Loop Input
4-20 mA in

DC 12 - 24 V

Power
Supply
Power
Supply

Example: Two transmitters connected to PLC/Recorder

with separate power supply

Transmitter 2

4
3
2
1

DC 12 - 24 V

Power
Supply
Power
Supply

Transmitter 1

4
3
2
1

Transmitter

           Terminals

4
3
2
1

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Transmitter

           Terminals

4
3
2
1

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

PLC or Recorder

Channel 1
4-20 mA in
Channel 1
4-20 mA in

Channel 2
4-20 mA in
Channel 2
4-20 mA in

* See AUX POWER Note

* See AUX POWER Note

* See AUX POWER Note

* See AUX POWER Note

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

Auxiliary Power note:

AUXILIARY power is used  only if the flow sensor requires more
than 1.5  mA current.  For Signet sensors this is limited to the
following products:

• 2000

• 2507

• 2530

• 2535

• 2540 if mfg. prior to Jan 1999

No Aux Power

515
525
2100
2517
2536
2540
3-8510-XX
3-8512-XX

Aux Power
2000
2507
2530
2535
2540 (mfg prior to Jan 1999)

Terminals

Sensr Gnd

(SHIELD)

Sensr IN

(RED)

Sensr V+

(BLACK)

9

8

7

Summary of Contents for 8550-1

Page 1: ...rrent output 4 to 20 mA isolated fully adjustable and reversible Flow Flow 6 25 GPM Total 1234567 8 ENTER 3 8550 090 1 1 Installation ProcessPro transmitters are available in two styles panel mount and field mount The panel mount is supplied with the necessary hardware to install the transmitter This manual includes complete panel mounting instructions Field mounting requires one of two separate m...

Page 2: ...ection Wiring Removal Procedure 1 Press the orange terminal lever downward with a small screwdriver to open terminal jaws 2 When fully open remove wire from terminal 2 1 Terminals 5 and 6 Open collector Output A transistor output programmable see CALIBRATE menu as High or Low setpoint with adjustable hysteresis Volumetric pulse Frequency based on flow rate May be disabled Off if not used Terminals...

Page 3: ...Loop Input 4 20 mA Loop Input 4 20 mA Internal PLC Connection Connection to a PLC Recorder separate supply PLC or Recorder Loop Input 4 20 mA in Loop Input 4 20 mA in DC 12 24 V Power Supply Power Supply Example Two transmitters connected to PLC Recorder with separate power supply Transmitter 2 4 3 2 1 DC 12 24 V Power Supply Power Supply Transmitter 1 4 3 2 1 Transmitter Terminals 4 3 2 1 Sys Pwr...

Page 4: ...lse that is relative to the flow volume or to the flow rate Low Output triggers when the flow rate is less than the setpoint The output will relax when the flow rate moves above the setpoint plus the hysteresis value High Output triggers when the flow rate is greater than the setpoint The output will relax when the flow rate drops below the setpoint plus the hysteresis value Frequency Output is a ...

Page 5: ... UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element will begin flashing Step 5 Press UP or DOWN keys to edit the flashing element RIGHT ARROW key advances the flashing element Step 6 Press ENTER key to s...

Page 6: ...sired mode of operation for the Open Collector output Options available are High Low volumetric Pulse or Frequency The signal may be disabled Off if not used In Low or High Mode the Open Collector output will be activated when the Flow rate reaches this value Be sure to modify this setting if you change the Flow Units The Open Collector output will be deactivated at Setpoint Hysteresis depending o...

Page 7: ...zer Lock On The Key Code must be entered to reset the resettable totalizer Adjust the minimum and maximum current output The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 mA Use this setting to match the system output to any external device Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active ...

Page 8: ...e place to the right Increase Pulse volume setting Decrease pulse width setting Reduce system flow rate Enter K factor from 0 0001 to 99999 Change the hysteresis value Replace transmitter SIGNET Signet Scientific Company 3401 Aerojet Avenue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website gfsignet com Or call in the U S 800 854 4090 G...

Reviews: