background image

7. Ordering 

Information

Mfr. Part No. 

Code 

 

Description

3-2350-1 

159 000 021 

Temperature sensor, (S

3

L) output, 

3

/

4

 in. NPT, 4.6 m (15 ft) cable

3-2350-3 

159 000 920 

Temperature sensor, 4 to 20 mA output, 

3

/

4

 in. NPT, 4.6 m (15 ft) cable

Accessories
Mfr. Part No. 

Code 

 

Description

3-8050-1 

159 000 753 

Universal mount junction box

3-8052   

159 000 188 

3

/

4

 in. Integral mounting kit

3-8052-1 

159 000 755 

3

/

4

 in. NPT mount junction box

3-9000.392-1 

159 000 839 

Liquid tight connector kit, NPT (1 piece)

3-9000.392-2 

159 000 841 

Liquid tight connector kit, PG13.5 (1 piece)

3-9900.396 

159 001 701 

Angle Adjustment Adapter Kit

5523-0322 

159 000 761 

Cable, 3 con shield, 22 AWG, black/red/white/shield

3-0250   

159 001 538 

USB to digital (S

3

L) con

fi

 guration/diagnostic tool

* Custom cable length available, contact the factory.

6.  4 to 20 mA Span Adjustment

The 4 to 20 mA endpoint values are independent of one another 
and may be adjusted in the 

fi

 eld.  For example, to reduce the 20 mA 

endpoint value from the factory setting of 100 °C, but to allow the 4 mA 
endpoint to remain at 0 °C, perform only the steps listed in 6.2 below.

NOTE:

 The RED wire, which is not connected during normal 

4 to 20 mA operation, assumes an important role in the 
following procedures.

6.1  To adjust the 4 mA endpoint in the fi eld:

•  Carefully remove the heat shrink tube protecting the red wire.
•  Expose the sensor to the temperature desired to correspond with 4 mA

-10 °C to 100 °C (submersible: -10 °C to 85 °C). 
(Be sure to allow suf

fi

 cient time for the sensor to reach equilibrium.)

+

-

3-8052

3-8050.521

Loop Input +

4 to 20 mA

loop monitor

Power Supply

DC 12 - 24 V

Black (Loop +)

Optional

Earth Ground

Loop Input -

Shield

White (Loop - )

Red

Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA  91731-2882  U.S.A.  •  Tel. (626) 571-2770  •  Fax (626) 573-2057
For Worldwide Sales and Service, visit our website:  www.gfsignet.com  •  Or call (in the U.S.):  (800) 854-4090
For the most up-to-date information, please refer to our website at www.gfsignet.com

3-2350.090-1   Rev. K  03/13    English 

 © Georg Fischer Signet LLC  2013

WARNING!

Not protecting the 
red wire may cause 
the 4 to 20 mA span 
to be reset.

Wire Nut

•  With power applied as described in Section 5, connect the RED wire to the WHITE wire for 15 seconds. 

(After about 10 seconds the output will drop to 3.6 mA and remain there until the RED wire is disconnected.)

•  Disconnect the RED wire from the WHITE wire; the 4 mA endpoint has been adjusted.

• NOTE:

 The output will act as a switch if the 4 and 20 mA endpoints are set very near to the same value.

6.2  To adjust the 20 mA endpoint in the fi eld:

•  Expose the sensor to the temperature desired to correspond with 20 mA -10 °C to 100 °C (submersible: -10 °C to 85 °C). 

(Be sure to allow suf

fi

 cient time for the sensor to reach equilibrium to this temperature.)

•  With power applied as described in Section 5, connect the RED wire to the BLACK wire for 15 seconds. 

(After about 10 seconds the output will rise to 22 mA and remain there until the RED wire is disconnected.) 

•  Disconnect the RED wire from the BLACK wire; the 20 mA endpoint has been adjusted.

NOTE

: The output will act as a switch if the 4 and 20 mA endpoints are set very near to the same value.

•  Minimum span is ±2% of maximum range.
•  After adjusting the 4 to 20 mA span, protect the red wire by installing the provided wire nut.
•  For easier re-spanning use the Signet 0250 USB to Digital (S

3

L) Con

fi

 guration/Diagnostic Tool.

6.3  To restore the factory setting:

•  Disconnect power to the sensor.  Wait 10 seconds for circuit to discharge.
•  Connect the RED wire to the WHITE wire.
•  Apply power as described in Section 5, but with the RED wire connected to the WHITE wire for 15 seconds.

(After about 10 seconds the output will drop to 3.6 mA and remain there until the RED wire is disconnected.)

•  Disconnect the RED wire from the WHITE wire; factory settings have been restored.

Mfr. Part No. 

Factory Span

3-2350-3 

4 to 20 mA = 0 °C to 100 °C 

Summary of Contents for 2350

Page 1: ... Cable type 3 cond shield 22 AWG Standard cable length 4 6 m 15 ft Shipping weight 0 22 kg 0 5 lb Electrical Power requirements S3 L models 5 VDC 10 1 5 mA 4 to 20 mA models 12 24 VDC 10 Short circuit reverse polarity protected Digital S3 L output Serial ASCII TTL level 9600 bps Accuracy 0 5 C 0 9 F Repeatability 0 1 C 0 2 F Resolution 0 01 C 0 02 F Update rate 100 ms 4 to 20 mA output Accuracy 32...

Page 2: ...the process connection Make sure the flow alignment indicator is in correct position in the pipe Damage to the sensor tip can occur if the sensor tip is installed improperly Install 8350 transmitter or 9900 refer to 8350 or 9900 manual for wiring information The 3 8052 Integral kit includes 3 4 in NPT process connection 3 9000 392 1 liquid tight connector 1 2 in NPT Conduit base to attach 8350 3 3...

Page 3: ...0 mA loop output when powered with 24 VDC Connecting the SHIELD to a direct Earth ground may reduce electrical noise interference Red wire is not used do not remove the heat shrink See Section 6 4 to 20 mA Span Adjustment 5 1 Current Loop With No Junction Box 5 2 Current Loop With Junction Box 3 8052 1 4 20 mA FREQ DATA WHT WHT BLU BLK N C RED SHIELD SENSOR INPUT SHIELD FREQ DATA White Black Power...

Page 4: ...signet com Or call in the U S 800 854 4090 For the most up to date information please refer to our website at www gfsignet com 3 2350 090 1 Rev K 03 13 English Georg Fischer Signet LLC 2013 WARNING Not protecting the red wire may cause the 4 to 20 mA span to be reset Wire Nut With power applied as described in Section 5 connect the RED wire to the WHITE wire for 15 seconds After about 10 seconds t...

Reviews: