background image

 2350 Temperature Sensor

3. Installation

The compact integral assembly can be installed using the 
following directions:

3.2   2350-3 In-line Remote Assembly

The optional 3-8052-1 Integral Junction box with ¾ in. process 
connection offers a convenient terminal point to extend the 2350 
cable over distances greater than 4.6 m (15 ft).
•  The kit includes:

•  ¾ in. NPT process connection
•  Conduit base and cap with junction terminals
•  3-9000.392-1 liquid tight connector, ½ in. NPT

To extend the wires longer than 4.6 m (15 ft):
•  Modify sensor 3-2350-1 or 3-2350-3 as described in 

fi

 gure 1.

•  Terminate the three wires to the terminal board located in the 

cap assembly.

•  Add customer-supplied wire to extend the cable.
•  Terminate to the transmitter or the 4 to 20 mA input device.
•  Apply sealant or PTFE tape to the process connection threads 

per 

fi

 gure 3, after inspecting threads to ensure integrity.

DO NOT install a sensor with damaged threads.

•  Tighten the sensor 1½ turns past 

fi

 nger tight into the process 

connection.

3.1  2350-1 Integral Assembly Sensor Modifi cation

•  Modify sensor part number 3-2350-1 per 

fi

 gure 1.

•  Apply sealant or PTFE tape to the process connection threads 

per 

fi

 gure 2, after inspecting threads to ensure integrity. Do not 

install a sensor with damaged threads.

•  Thread the sensor into the 3-8052 mounting kit.
•  Tighten the sensor 1½ turns past 

fi

 nger tight into the process 

connection.

•  Make sure the 

fl

 ow alignment indicator is in correct position in 

the pipe. Damage to the sensor tip can occur if the sensor tip is 
installed improperly.

•  Install 8350 transmitter or 9900

(refer to 8350 or 9900 manual for wiring information).

•  The 3-8052 Integral kit includes:

• 

3

/

4

 in. NPT process connection

•  3-9000.392-1 liquid tight connector, 

1

/

2

 in. NPT

•  Conduit base to attach 8350.

3.3  2350-1 or 2350-3 Submersible Installation

•  Use the 2350-1 or 2350-3 sensor with 4.6 m (15 ft) cable.
•  Mount the sensor to an extension pipe or watertight conduit 

using thread sealant.

•  Use a cable gland at the top of the extension to prevent 

moisture intrusion/accumulation inside the pipe.

•  For additional defense against possible accumulation of 

condensation at the back seal area of the sensor, 

fi

 ll the lower 

75 mm to 100 mm (3 in. to 4 in.) of conduit or extension pipe 
with a 

fl

 exible sealant such as silicone.

4-20

mA

FREQ/

DA
T

A

WHT

W
HT

BLU

B

LK

N/C

R

ED

SHIELD

SENSOR

INPUT

*

SHIELD

+

FREQ/

DA
T

A

3-8052-1

Integral junction box,
3/4 in. NPT

*Customer supplied extension cable
must not exceed 305 m (1000 ft.)

*

3-8052

Integral mount kit

3-9900
3-8350

3-9900.396
Angle Adjustment Adapter Kit

*Customer supplied extension cable
must not exceed 305 m (1000 ft.)

152 mm

(6 in.)

Figure 1

Figure 2

Figure 3

Fill with
3 to 4 in.
of sealant

‡MXQFWLRQER[UHFRPPHQGHG

Align with
flow stream

Flow

NOTE:

The 8050-1 or the 8052-1 junction boxes can be useful 
accessories for this installation option.

CAUTION!

The 

fl

 uid temperature must not exceed 85 °C (185 °F) 

in submersible installations.

Summary of Contents for 2350

Page 1: ... Cable type 3 cond shield 22 AWG Standard cable length 4 6 m 15 ft Shipping weight 0 22 kg 0 5 lb Electrical Power requirements S3 L models 5 VDC 10 1 5 mA 4 to 20 mA models 12 24 VDC 10 Short circuit reverse polarity protected Digital S3 L output Serial ASCII TTL level 9600 bps Accuracy 0 5 C 0 9 F Repeatability 0 1 C 0 2 F Resolution 0 01 C 0 02 F Update rate 100 ms 4 to 20 mA output Accuracy 32...

Page 2: ...the process connection Make sure the flow alignment indicator is in correct position in the pipe Damage to the sensor tip can occur if the sensor tip is installed improperly Install 8350 transmitter or 9900 refer to 8350 or 9900 manual for wiring information The 3 8052 Integral kit includes 3 4 in NPT process connection 3 9000 392 1 liquid tight connector 1 2 in NPT Conduit base to attach 8350 3 3...

Page 3: ...0 mA loop output when powered with 24 VDC Connecting the SHIELD to a direct Earth ground may reduce electrical noise interference Red wire is not used do not remove the heat shrink See Section 6 4 to 20 mA Span Adjustment 5 1 Current Loop With No Junction Box 5 2 Current Loop With Junction Box 3 8052 1 4 20 mA FREQ DATA WHT WHT BLU BLK N C RED SHIELD SENSOR INPUT SHIELD FREQ DATA White Black Power...

Page 4: ...signet com Or call in the U S 800 854 4090 For the most up to date information please refer to our website at www gfsignet com 3 2350 090 1 Rev K 03 13 English Georg Fischer Signet LLC 2013 WARNING Not protecting the red wire may cause the 4 to 20 mA span to be reset Wire Nut With power applied as described in Section 5 connect the RED wire to the WHITE wire for 15 seconds After about 10 seconds t...

Reviews: