Technical Manual of Micro Data Center

Data Centers for the EDGE

www.signamax.com

Summary of Contents for MicroDC

Page 1: ...Technical Manual of Micro Data Center Data Centers for the EDGE www signamax com ...

Page 2: ...ing unit 9 2 3 Mains Power Supply Line 10 3 Installation 11 3 1 Required Setup Equipment 11 3 2 Cabinet Installation 11 3 3 Cooling Unit 17 3 4 Secondary Equipment 19 4 Maintenance 20 4 1 Cooling device 20 5 Troubleshooting 21 5 1 Wheels 21 5 2 Cooling 22 6 Service Log 24 7 Certificates 25 www signamax com Micro Data Center Technical Manual 2 ...

Page 3: ...densing Install the product in a clean environment free from dust moisture flammable liquids gases and corrosive substances Whereapplicable thisproductmustbepermanentlyconnected and powered from a suitable single phase AC supply rated in accordance with the equipment data plate It must be suitably grounded and protected by a circuit breaker or fuse A residual current device commonly known as diffe...

Page 4: ...IPTION A İLK ÜRETİM ÖĞE NO PARÇA NUMARASI 1 02 1035 M 00 24U 1000mm S 2 484 16023 AABA Sugatsune GX 3 484 16023 BABA Sugatsune GX 4 021607M00 24U 800mm CON 5 021610M00 24U BENRADUSLU 6 021740P00 ALM 24U 19 7 021874M00 MİCRO DC ALT Ü 8 021894M00 19 HAVA YONLEND 9 021895M00 IP54 24U 800X 10 025124H00 4K 11 484073335012 CİVATA M5 12 TSB K DRAWN CHK D MFG Q A FINISH KESKİN KENAR VE ÇAPAK OLMAYACAKTIR ...

Page 5: ...d to a third party without written consent of the proprietor KORAY Alemdağ Cad No 169 81257 Ümraniye İSTANBUL www canovate com ELEKTRONİK ENDÜSTRİ TİCARET A Ş Bu dökümanın içeriği CANOVATE in mülkiyetinde olup yazılı izin alınmadan kopya edilemez aynı biçimde oluşturulamaz ve üçüncü şahıslara açıklanamaz 26 Eylül 2014 Cuma 14 14 27 E pdmview canovate Standart Urunler 05 Micro Datacenter Kab 13 Ağu...

Page 6: ...g unit comes in two versions version one is 2KW cooling capacity version two is 3 8 KW cooling capacity The second way is to feed the cooling unit from a dedicated power line from any available electrical distribution panel It is strongly recommended to use the second option and feed the system by a separated power line In chapter 4 3 there is brief explanation on what kind of circuit breaker shal...

Page 7: ...e generated noise mainly coming from the embedded compressor might be annoying Please avoid placing the MicroDC close to any infants Please visit the room where the MicroDC stands quite often especially after the first installation to secure that the environmental conditions meet the operating limits 2 3 Mains Power Supply Line A clean unloaded and direct single phase power supply line shall be pr...

Page 8: ...ration Install the MicroDC in a computer room or in any other room where people are normally present only for maintenance 3 1 Required Setup Equipment The following tools are required to set up your MicroDC Pallet jack Utility knife Allen key number 4 ratchet or wrench Torx screwdriver T25 ratchet or wrench Measuring tape and pen marker able to write on metal surfaces Spirit Level hammer Flathead ...

Page 9: ...alid whenever a transportation mishandling has damaged the MicroDC The MicroDC is standing on a wooden pallet All the way round there are lots of thick cartons used for protection of the cabinet against possible damage to the surface color Overall these carton vertical lines there is nylon or bubble nylon used for protection against dust insects or any other small similar intrusions Step 1 Remove ...

Page 10: ...l take care not to scratch the color of the MicroDC cabinet Step 3 Remove all carton pcs surrounding the MicroDC Those cartons are loose so there is no need to use any tool at the moment Please recycle all the carton parts used for the packaging www signamax com Micro Data Center Technical Manual 10 ...

Page 11: ...t as possible Release the brakes on the wheels if available Then grab the MicroDC gently and carefully slide it down so it can slowly move to the floor After the MicroDC has left the wooden pallet is ready to be placed at its final position Note Known the weight and size of the MicroDC it is possible that the MicroDC may tip over while moving The MicroDC must be removed from the shipping crate usi...

Page 12: ... inch 483 or 533mm rack rails These internal mounting rails will be either center mount rails or front and rear mount rails that are designed in accordance with the EIA 310D or EIA 310E rack standard Both types are adjustable for equipment of different sizes There are two pairs of mounting rails inside the MicroDC the front pair and the rear pair The distance in between the 2 vertical rails in a s...

Page 13: ... rails This will prevent the installer from any injures such as electrical shock 3 2 4 Mounting Hardware Optional mounting clip nuts and screws are available for mounting equipment to the mounting rails Clip nuts are a clip with a captive nut that fits over vertical rack rail holes allowing individual placement of the mounting hardware Each clip nut and screw package includes 10 clip nuts Type 10 ...

Page 14: ...le 2KW edition According to the technical datasheet of the Air Condition Unit the maximum absorbed power is 1300W which makes a current around 6 Ampere As per the manufacturer a fuse of 10A 16A rated shall be used Please pay attention this circuit breaker must be rated tripping B with equal or more Recommended Equipment Stacking Arrangement Return Air Return Air Return Air Blowing Air Blowing Air ...

Page 15: ...ower then it is ready and operational There is no embedded switch so after turning the external circuit breaker to ON position then the cooling device will start immediately The factory temperature setting is usually at 35 degrees Celsius 95 F Note Please refer to the respective user manual of the cooling unit for detailed information on how to operate and interfere to the default settings Inside ...

Page 16: ...ty having Jurisdiction in the end use application Signamax offers different models of CSA Certified PDU s if required as part of Micro DC Solution They are available in single phase but also three phase power input options The units may be used in 120V 208 240V or 230V applications with almost every type of connectors including NEMA or IEC type they are available in basic type metered and with or ...

Page 17: ... embarking on any maintenance work switch current off of the cooling unit The cooling unit is a low maintenance type so no filter change is required The main job that regularly needed to be done is to blow the internal components with compressed dry air at a maximum pressure of 4 bars the following also shall be checked regularly Job Frequency Check the external air to air heat exchanger and clean...

Page 18: ...t able to move It is very difficult the movement of MicroDC The version does not include wheels Please unload the MicroDC to become lighter and then relocate the standing position The wheels are dirty Clean the wheels by remov ing all attached dust and dirt You may use a lubricant spray as well The brakes where available are preventing from sliding Release the brakes and then try to move the Micro...

Page 19: ...ompressor does not work Compressor s amperometric protector failed external to the compressor where present Relay or PTC for compres sor starting failed Capacitor for compressor starting failed where pres ent Compressor motor electrical failure High pressure safety switch failed Compressor contactor failed where present This is not a malfunction of the cooling unit To verify functioning when testi...

Page 20: ...condenser either dirty or clogged Ventilate the premises where the enclosure is installed to keep ambient temperature lower Clean the exchanger with compressed air and detergent Thermal protector inside the compressor triggered Ambient temperature over the maximum working limit Heat exchanger coil condenser either dirty or clogged Ventilate the premises where the enclosure is installed to keep amb...

Page 21: ...mirates T 97 155 424 2722 E ME signamax com SOUTH EAST ASIA 55 UBI Ave 1 02 10 UBI 55 Singapore 408935 T 65 6925 5798 E FE signamax com CANADA 2 975 Bleams Rd Kitchener Ontario Canada N2E3Z5 T 1 519 570 3911 E CA signamax com MALAYSIA Suite 1 2 1st Floor Bangunan THK No 2A Jalan 243 Seksyen 51a 46100 Petaling Jaya Selangor Malaysia T 60 3 7873 7317 E mei signamax com SRI LANKA 49 Sri Jinarathana R...