![SignalFire MBS-CBBL Interface Manual Download Page 12](http://html.mh-extra.com/html/signalfire/mbs-cbbl/mbs-cbbl_interface-manual_1268324012.webp)
Rev 5.8
SignalFire Telemetry
12
Remote Modbus Register Mapping
In addition to any pre-configured registers, the Modbus Stick will send system
information in 16-bit registers in the table below. This data is accessible at any of the one
or more Slave IDs connected to the Modbus Stick.
Register
Register Address
(Offset)
Description
49986
9985 or 65522
Checkin Interval (in seconds)
49987
9986 or 65523
Low Battery Alarm (0=no errors, 1=low battery)
65524
9987 or 65524
Major revision number for the mainboard
65525
9988 or 65525
Minor revision number for the mainboard
65526
9989 or 65526
Major revision number for the radio
65527
9990 or 65527
Minor revision number for the radio
65528
9991 or 65528
High 16 bits of SFTS node address
65529
9992 or 65529
Low 16 bits of SFTS node address (the radio ID)
65530
9993 or 65530
Slave ID readback
65531
9994 or 65531
Received signal strength of last packet from the slave
65532
9995 or 65532
System voltage of the Modbus client in millivolts
65533
9996 or 65533
Minutes until this slave will time out, unless new data is received
65534
9997 or 65534
Number of registers cached for this slave device
65535
9998 or 65535
Remote device type (0 for Modbus Client Node)
Revision History
Revision
Date
Changes/Updates
5.4
7/23/13
5.5
6/24/15
Updated Design
5.6
8/3/16
Added section on encryption
5.7
3/31/20
Remote Modbus R/W
5.8
7/9/2020
Updated Modbus program steps menu, new checkin register