![SIGNAL FIRE GWS-CBBL Interface Manual Download Page 25](http://html1.mh-extra.com/html/signal-fire/gws-cbbl/gws-cbbl_interface-manual_1268237025.webp)
Rev 4.9
SignalFire Telemetry
25
Modbus Gateway Register Map
The SignalFire Modbus Gateway by default is assigned Modbus ID number 247.
Only the
Gateway status/configuration and remapped registers are read at this address.
All
remote node registers are read from the Modbus ID and register address of the remote node
unless Modbus register remapping is used. If the gateway has a large total number of registers
approaching 4700, register 2008 should be monitored to ensure that free registers are available before adding
a new node.
Coils
Read coils with Modbus opcode 0x01 (Read Coil). Write coils with Modbus opcode 0x05 (Write Single Coil) or
0x15 (Write Multiple Coils).
Register
Address
Register
Number
Description
R/W
0000
00001
System Reset: Resets the gateway and radio
R/W
0001
00002
Radio Reset: Resets the radio leaving the gateway on
R/W
0002
00003
Counter Reset: Resets all GW status counters to zero (See Read Only Registers
2026-2031)
R/W
0101
00102
Analog/Relay Output Module 1 Relay 1
R/W
0102
00103
Analog/Relay Output Module 1 Relay 2
R/W
0103
00104
Analog/Relay Output Module 2 Relay 1
R/W
0104
00105
Analog/Relay Output Module 2 Relay 2
R/W
0131
00132
Digital Output Module 1 Relay 1
R/W
0132
00133
Digital Output Module 1 Relay 2
R/W
0133
00134
Digital Output Module 1 Relay 3
R/W
0134
00135
Digital Output Module 1 Relay 4
R/W
0135
00136
Digital Output Module 1 Relay 5
R/W
0136
00137
Digital Output Module 1 Relay 6
R/W
0137
00138
Digital Output Module 1 Relay 7
R/W
0138
00139
Digital Output Module 1 Relay 8
R/W
0139
00140
Digital Output Module 1 Relay 9
R/W
0140
00141
Digital Output Module 1 Relay 10
R/W
0141
00142
Digital Output Module 1 Relay 11
R/W
0142
00143
Digital Output Module 1 Relay 12
R/W
0143
00144
Digital Output Module 2 Relay 1
R/W
0144
00145
Digital Output Module 2 Relay 2
R/W
0145
00146
Digital Output Module 2 Relay 3
R/W
0146
00147
Digital Output Module 2 Relay 4
R/W
0147
00148
Digital Output Module 2 Relay 5
R/W
0148
00149
Digital Output Module 2 Relay 6
R/W
0149
00150
Digital Output Module 2 Relay 7
R/W
0150
00151
Digital Output Module 2 Relay 8
R/W