SDM 081
S-DIAS SAFETY DIGITAL MIXED MODULE
Page 14
07.02.2022
3
Technical Data
3.1
Input Specifications
The inputs are Type 1 in accordance with EN 61131-2
Number
6
Input voltage
+24 V DC
Input voltage range
m18 V
m30 V
(1)
Signal level
low: ≤ +5 V
high: ≥ +15 V
Switching threshold
typ11 V
Input current
3 mA at +24 V
Input delay
0.5 ms
(1)
With increased ambient temperature >55 °C the maximum permissible supply voltage is
reduced from 30 V to 28.8 V.
3.2
Specifications for Cross-Circuit Detection Signal Outputs
Number
3x signal A
3x signal B
Rated output voltage
+24 V DC
Output voltage range
m18 V
m30 V
(2)
Output current
100 mA at +24 V
Miscellaneous
short-circuit proof
(2)
With increased ambient temperature >55 °C the maximum permissible supply voltage is
reduced from 30 V to 28.8 V.
The clock outputs A and B are generated once internally and are wired in parallel to
the connectors. A direct cross-circuit of Clock A and/or B of a connector therefore
results in cross-circuit detection in all channels.
When using the digital inputs with the clock outputs for cross-fault detection for long
cable lengths, make sure that the cable capacitance from the clock output to the
digital input does not exceed a value of 100 nF and that the cable resistance does not
exceed a value of 250 Ω, so that the cross-fault detection does not detect a wiring
error with proper wiring.
Summary of Contents for SDM 081
Page 21: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 19...
Page 23: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 21 4 Mechanical Dimensions...
Page 27: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 25 6 Wiring 6 1 Wiring Example...
Page 35: ...S DIAS SAFETY DIGITAL MIXED MODULE SDM 081 07 02 2022 Page 33 9 3 Example...