S-DIAS CPU MODULE
CP 313
29.05.2020
Page 37
70 ..
C-DIAS ERROR
A connection error with a C-DIAS
module has occurred.
Cause:
-
The cause of the error is
documented in the log file
Solution:
-
This depends on the cause
72
S-DIAS ERROR
A connection error with an S-DIAS
module has occurred.
Possible Causes:
-
Real network does not match the
project
-
S-DIAS client is defective
Solution:
-
Analyze log file
75
SRAM ERROR
An error occurred while initializing,
reading or writing SRAM data.
Possible Causes:
-
SRAM configured incorrectly
-
Battery for powering the internal
program memory is empty
Solution:
-
Analyze log file (Event00.log,
Event19.log)
-
Check configuration
-
Exchange battery for powering
the internal program memory
97
USER DEFINED 2
User-definable code.
98
USER DEFINED 3
User-definable code.
99
USER DEFINED 4
User-definable code.
100
C_INIT
Initialization start; the configuration is
run.
101
C_RUNRAM
The LASAL project was successfully
started from RAM.
102
C_RUNROM
The LASAL project was successfully
started from ROM.
103
C_RUNTIME
104
C_READY
The CPU is ready for operation.
105
C_OK
The CPU is ready for operation.
106
C_UNKNOWN_CID
An unknown object from a stand-alone
or embedded object, or an unknown
base class was detected.
Summary of Contents for 20-004-313
Page 15: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 13...
Page 17: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 15 5 Mechanical Dimensions...
Page 30: ...CP 313 S DIAS CPU MODULE Page 28 29 05 2020 9 Wiring 9 1 Wiring Example...
Page 33: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 31 10 Process Diagram...