S-DIAS CPU MODULE
CP 313
29.05.2020
Page 17
6.1
Status LEDs Interface Part
Run
green
ON
from activation of the voltage supply until processing of the
autoexec.lsl
when the application is running (except when controlled differently
via the application )
BLINKS
In the CLI, while processing the autoexec.lsl until the application is
running
During installation of the operation system (starting from OS
version 09.03.054)
OFF
when error occurs
reset-state
Permanent from power on: microSD card error
(1)
can be set from the application (ON, BLINKING, OFF)
Status
yellow
OFF
during start process
during RUN status (application running)
when error occurs or reset
Permanent from power on: microSD card error
(1)
can be set from the application (ON, BLINKING, OFF)
Error
red
BLINKS
when an error or reset occurs
OFF
during start process
during RUN status (application running)
Permanent from power on: microSD card error
(1)
can be set from the application (ON, BLINKING, OFF)
VARAN Link
green
ON
connection between the two PHYs made
BLINKS
VARAN In of the primary client has no link
VARAN Active
yellow
ON
data is exchanged over the VARAN bus
Ethernet Link
green
ON
connection between the two PHYs made
Ethernet Active
yellow
ON
data is exchanged over the Ethernet bus
EtherCAT Link
green
ON
connection between the two PHYs made
EtherCAT Active
yellow
ON
Data is exchanged over the EtherCAT bus
(1)
If the microSD card is not properly inserted or if data (operating system, application) is faulty, the RUN, STATUS
and Error LEDs do not light up after switching on the power supply. The DC OK LED lights up permanently.
Summary of Contents for 20-004-313
Page 15: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 13...
Page 17: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 15 5 Mechanical Dimensions...
Page 30: ...CP 313 S DIAS CPU MODULE Page 28 29 05 2020 9 Wiring 9 1 Wiring Example...
Page 33: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 31 10 Process Diagram...