- 16 -
Ph 2
Central heating pup launch hysteresis
1
10
1
˚
C 2
Pc 2
Pause time of central heating pump with
30 sec. work periods
--,1 99 1min 2
u 50
Tap hot water desired temperature
30
60
1
˚
C 50
uh 5
hot water heating hysteresis
1
9
1
˚
C 5
ur 0
No hot water-0, hot water priority-1, no
hot water priority-2, mixing pump-3
0 2 1 0
L 40
Minimum boiler temperature
30
65
1
˚
C 40
H 90
Maximum boiler temperature
80
90
1
˚
C 90
h 5
Boiler temperature hysteresis
1
10
1
˚
C 5
A 99
Boiler overheating temperature
90
99
1
˚
C 99
Fd60
Fuel shortage testing time with burning,
increase by 5
˚
C
1 99
1min 60
Fb30
Fuel shortage testing time in WORK
mode and burning out.
1 99
1min 30
Ar 0
Additional output: 0-FUEL, 1-ALARM, 2-
MIX
0 2 1 0
Prod
Return to factory defaults after pressing
OK
outP
Central heating pump output testing,
press OK - launch
outP out1
out
∏
Fan output testing, press OK - launch
out
∏
out2
outr
Oil boiler launch output testing, press OK
– launch boiler
outr out3
outu
Hot water pump output testing, press OK
- launch
outr out4
End
Exit the service mode after pressing OK
In the table above, the first column represents example display indications, in
the next columns there are: parameter description, minimum and maximum
values allowed to set, step of the parameter during the setup. The last column
shows factory defaults to which you can return by choosing [Prod] option.
(1) Fan work parameters
Fan power [
Π
100] - this value defines power of the fan. When "
Π
r" parameter is
set to "0-10" this is the maximum power of the fan which can be achieved
during automatic fan control.
Automatic fan speed control [
Π
r 1] - it is on, when this parameter is set to "0-10"
and causes automatic fan speed decrease when temperature of water in the
boiler reaches desired temperature. If this parameter is set to "-", the fan
automatic smooth speed control is disabled and the fan can work with power set
by "
Π
" parameter. Setting parameter value in range from 0 to 10 means time in
minutes of the smooth fan speed increase from 40% to value of "
Π
" - for smooth
boiler start.