- 30 -
A.G.M 1
56.4
53.6
A.G.M 2
58.4
54.8
Sealed Lead Acid
57.6
54.4
Gel Euro
57.6
55.2
Open Lead Acid
59.2
53.2
Calcium
60.4
53.8
De-sulphation
62V for 4hrs
Bypass &
Protectio
n
Input Voltage
Waveform
Sine wave (Grid or Generator)
Nominal Phase
Voltage
120Vac
220Vac
Low Voltage Trip
70V/96V±4%
184V/154V±4%
Low Voltage re
engage
75V/100V±4%
194V/164V±4%
High Voltage Trip
130V±4%
253V/260V±4%
High Voltage re
engage
135V±4%
243V/270V±4%
Max Input AC
Voltage
150VAC
300VAC
Nominal Input
Frequency
50Hz or 60Hz (Auto detect)
Low Freq Trip
Narrow: 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz Wide:40±0.3Hz for 50Hz/60Hz
Low Freq re engage
Narrow: 48±0.3Hz for 50Hz, 58±0.3Hz for 60Hz Wide:42±0.3Hz for 50Hz/60Hz
High Freq Trip
Narrow: 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz Wide:70±0.3Hz for 50Hz/60Hz
High Freq re
engage
Narrow: 54±0.3Hz for 50Hz, 64±0.3Hz for 60Hz Wide:68±0.3Hz for 50Hz/60Hz
Output Short circuit
protection
Circuit breaker
Bypass breaker
rating(230Vac)
10A
20A
30A
40A
50A
60A
80A
Bypass breaker
rating(120Vac)
20A
40A
60A
Other
Communication
methods
RS232/458/CAN
Display
LED+LCD
Unit Size
804*620*263m
m
804*620*263m
m
804*620*263m
m
650*513*803mm
650*513*803mm
650*513*803mm
760*513*848mm
Package Size
980*730*370m
m
980*730*370m
m
980*730*370m
m
800*670*1000m
m
800*670*1000m
m
800*670*1000m
m
930*670*1100m
m
Net Weight KG
70
105
120
175
190
210
270
Gross Weight KG
85
120
135
205
220
240
300
Updated on
20201117