www.sigineer.com
21
05 Battery Type
AGM Battery (Default)
05 Battery Type
Flood Battery
05 Battery Type
User-Defined
05 Battery Type
User-Defined 2
05 Battery Type
Lithium
06 Automatic Overload Restart Restart Disable (Default)
06 Automatic Overload Restart
Restart Enable
07 Automatic OverTemp
Restart
Restart Disable (Default)
07 Automatic OverTemp
Restart
Restart Enable
08 AC Output Voltage
230V (Default)
09 AC Output Frequency
50Hz (Default)
10 Number of 12V Batteries
Connected In Series
The default value is 4 for
48V model, and 2 for
24Vdc model.
11 Maximum Utility Charging
Current
10A to Max(default 30A)
12 DC to AC Transfer Voltage Default 46.0V,
44.0V~51.2V resettable,
12 DC to AC Transfer Voltage Lithium mode: default
40%, 5%~50% resettable
13 AC to DC Transfer Voltage Default 54.0V,
48.0V~58.0V resettable,
13 AC to DC Transfer Voltage Li mode: default 80%,
60%~100% resettable
14 Charger Power Source
Priority
Solar Priority
14 Charger Power Source
Priority
Solar and Utility
(Default)
14 Charger Power Source
Priority
Solar Only
15 Alarm On/Off Control
Audible Alarm on
(default)
15 Alarm On/Off Control
Audible Alarm off(Mute)
16 Backlight On/Off Control
Backlight on (default)
Summary of Contents for MS6048D
Page 6: ...www sigineer com 4...