Appendix A.
Battery Level Limits
Monitoring is stopped, and the system turns off automatically if the
battery state of charge falls to the BAT EMPTY level. For automatic
restart of monitoring, a higher level or external power is needed.
The reason for this shut-down mechanism is to prevent data loss and to
protect the batteries from permanent damages.
Falling voltage:
SOC
11
Display symbol
BAT FULL => BAT NORMAL
95% green scale
BAT NORMAL => BAT LOW
15% yellow scale
BAT LOW => BAT CRITICAL
5%
red scale, ticked
BAT CRITICAL => BAT EMPTY
0%
red outline
Rising voltage:
BAT EMPTY => BAT CRITICAL
2%
red ticked scale, ticked outline
BAT CRITICAL => BAT LOW
7%
yellow scale, ticked outline
BAT LOW => BAT NORMAL
17% green scale
BAT NORMAL => BAT FULL
97% green full scale
If one of the two batteries is removed, the indicated SOC level will be
halved and the warning message “BATTERY LOST” will be
communicated.
If the SOC level of the two batteries differs more than 15%, the warning
message “UNBALANCED” will be communicated.
Service messages are sent when the SOC level falls below the BAT LOW
or BAT CRITICAL levels.
For replacement of the backup battery, send the instrument to Sigicom.
11
SOC = State-Of-Charge (a combined state of charge of the two batteries).