![Sifam Tinsley N32P User Manual & Quick Start Download Page 25](http://html.mh-extra.com/html/sifam-tinsley/n32p/n32p_user-manual-and-quick-start_1267045025.webp)
EN
25
• Maximum load resistance
500 Ω
• Maximum current value
24 mA
• Intrinsic error
0.1% of range
• Error due to temperature change
50% of intrinsic error value / 10 K
Rated operating conditions
• Supply voltage
(depends on the version)
85...253 V AC (40...400 Hz),
90...300 V DC
or 20...40 V AC (40...400 Hz),
20...60 V DC
• Power consumption
< 6 VA
• Working temperature
-20...
23...+55 ºC
• Storage temperature
-30...70 ºC
• Humidity
< 95% (no condensation)
• Working position
any
• Pre-heating time
15 minutes
Protection grade ensured
• From the front
IP65
• From the terminals side
IP10
Weight and dimensions
• Meter weight
< 0.2 kg
• Dimensions (see Fig. 2)
96 x 48 x 93 mm
electromagnetic compatibility
• Noise immunity:
acc. to EN 61000-6-2
• Noise emission:
acc. to EN 61000-6-4
Safety requirements acc. to en 61010-1
• Circuit-to-circuit insulation:
basic
• Installation category:
III
• Pollution grade
2
• Maximum phase-to-earth operating voltage:
300 V for the measurement circuits.
300 V for the circuits: supply, alarm.
50 V for the circuits: auxiliary supply, RS-485 interface, analog
output
• Altitude a.s.l. < 2000 m