Sifam Tinsley N20ZPLUS User Manual Download Page 16

N20Z

PLUS

User’s Manual 

 15

 

- humidity  <95% (condensation of water vapor unacceptable)

- operation position:      any 

Sustained overload capacity:

  120 % Un, 120 % In 

Short duration overload capacity (3 s): 

voltage input       2 Un (<1000 V) 

current input:  

10 In 

Readout field: 

5 three-colour LED displays: 

digit height: 

14 mm 

colors: 

green, orange, red 

Indication range: 

-19999...99999

Ensured degree of protection from frontal side 

IP 65 acc. to EN 60529 

Dimensions: 

96 x 48 x 64 mm (including terminals) 

Weight:

 < 0.25 kg 

Power consumption:

  < 6 VA 

Electromagnetic compatibility 

immunity to electromagnetic interference according to EN 61000-6-2

emission of electromagnetic disturbances according to EN 61000-6-4

Safety requirements according to EN 61010-1: 

insulation between circuits: basic,

installation category III (for 400 V version 

– category II),

degree of pollution 2,

maximum operating voltage relative to earth:

- for supply circuit 300 V,

- for measuring input 480 V

- for RS485 interface 50 V

altitude < 2000 m.

Summary of Contents for N20ZPLUS

Page 1: ...DIGITAL PANEL METER N20ZPLUS USER S MANUAL ...

Page 2: ... 5 1 Display description 5 5 2 Messages after Switching the Supply on 5 5 3 Configuration of the meter 5 5 4 Parameter description 6 5 4 1 Display 6 5 4 2 Measurement parameters 6 5 4 3 Alarm parameters 8 5 4 4 Communication parameters 9 5 5 Factory parameters 9 6 MAP OF MODBUS REGISTERS 10 7 ERROR CODES 13 8 TECHNICAL DATA 14 9 ORDERING CODES 16 ...

Page 3: ...grammed are as follows display color individually in three colour versions thresholds of displayed exceedings result display precision decimal point backlight rtype of the measured signa AC or AC DC True RMS averaging time of the measurement recounting of indications individual characteristic operation modes of two OC type outputs 6 operating modes to choose RS 485 transmission parameters MODBUS b...

Page 4: ...pectations Possible consequences when these instructions are not followed In terms of operational safety the meter meets the requirements of EN 61010 1 Safety instructions The assembly and the installation of the electrical connections may be carried out only by a duly qualified electrician Before turning on the meter verify the connections Removal of the meter housing during the warranty period v...

Page 5: ...ge supply disconnected Before the insertion into the panel one must check the correct placement of the seal After inserting into the hole fix the meter by means of clamps Fig 2 1 2 Fig 2 Meter fitting Fig 3 Meter overall dimensions 4 1 Connection diagrams Fig 4 Electrical connections of the N20ZPLUS meter for voltage and frequency measurements Fig 5 Electrical connections of the N20ZPLUS meter for...

Page 6: ...tantaneous value from 1 measurement is displayed signaled by the backlit indicator of instantaneous value In the event of an error or exceeding the range value the display will show the message described in point 6 Exceeding the measurement range is additionally signaled by the instantaneous value indicator 5 3 Configuration of the meter To configure the N20ZPLUS meter the user can use free eCon s...

Page 7: ...pdated Fig 7 display color configuration b decimal point measurement precision There are 5 possible display configurations to choose from but you should take the accuracy of the measurement into account for example for the 400 V range the measurement error is 2 V so choosing a precision with two decimal places does not give you more accurate measurements For version with voltage measurement the fa...

Page 8: ... 5 s 1 min 100 every 0 6 s 2 min 100 every 1 21 s 5 min 100 every 3 s 7 min 100 every 4 2 s 12 min 100 every 6 s 15 min 100 every 9 1 s c Thresholds for displayed exceedings You can narrow the limits beyond which the exceedings will be displayed taking into account individual characteristics If the measured value is outside the measurement range 0 120 of the nominal value e g for the 400 V version...

Page 9: ...the equation according to the rule Coefficients A and B are individual characteristics parameters 5 4 3 Alarm parameters Two alarms are available in the N20ZPLUS meter Both work independently and each of them has 6 operating modes n on n off on off hon and hoff which are shown in Figure 9 The alarm thresholds Aoff and Aon are set in the values of the measured value taking into account the individu...

Page 10: ...o configure the correct communication address on the Modbus can take values from the range 1 247 baudrate available options 4800 9600 19200 38400 57600 115200 bps transmission mode available options 8N2 8E1 8O1 8N1 5 5 Factory parameters Table 2 Parameter description Range Value Default value The display color of the upper measured value red green orange red U I f The display color of the middle m...

Page 11: ...Hz Lower switching value of alarm 1 Aon 19999 99999 100 of the nominal value Un In or 49 Hz Alarm 1 switching delay 0 120 0 seconds Function of the alarm output 2 n on n off on off h_on h_off n on U I off f Upper switching value of alarm 2 Aon 19999 99999 110 of the nominal value Un In or 51 Hz Lower switching value of alarm 2 Aon 19999 99999 100 of the nominal value Un In or 49 Hz Alarm 2 switchi...

Page 12: ...isplay precision 0 00000 1 0000 0 2 000 00 3 00 000 4 0 0000 4001 RW Unit backlight 0 off 1 on 4002 RW Display color for values below the KpL threshold Fig 7 set in register 7603 0 orange 1 red 2 green 4003 RW Display color for values between KpL and KpH thresholds Fig 7 set in registers 7602 and 7603 0 orange 1 red 2 green 4004 RW Display color for values above the KpH threshold Fig 7 set in regi...

Page 13: ...Not applicable 4016 R Reserved Not applicable 4017 R Reserved Not applicable 4018 R Serial number of the meter older 16 bits of 32 bit value Not applicable 4019 R Serial number of the meter younger 16 bits of 32 bit value Not applicable 4020 RW Address of the Modbus device change requires acceptance by making an entry into the register 4023 0 247 4021 RW Baudrate change requires acceptance by maki...

Page 14: ...threshold of alarm 2 triggering 19999 99999 7608 RW Upper threshold of the color change of the KpH display pt 5 4 1 a 19999 99999 7609 RW Lower threshold of the color change of the KpL display pt 5 4 1 a 19999 99999 7610 R Measured value of the input signal frequency Not applicable 7611 R Measured value of the input signal U I Not applicable 7 ERROR CODES After switching the meter on error message...

Page 15: ...range 1 digit in the 20 500 Hz frequency range frequency 0 02 of the range 1 digit Additional errors in rated operating conditions due to changes in ambient temperature 50 of intrinsic error 10 K Averaging time voltage current programmable min 0 5 s default 1 s frequency non programmable 1 s Alarm outputs OC output type 30 V 20 mA passive acc to EN 62053 31 Serial interface RS 485 address 1 247 mo...

Page 16: ... frontal side IP 65 acc to EN 60529 Dimensions 96 x 48 x 64 mm including terminals Weight 0 25 kg Power consumption 6 VA Electromagnetic compatibility immunity to electromagnetic interference according to EN 61000 6 2 emission of electromagnetic disturbances according to EN 61000 6 4 Safety requirements according to EN 61010 1 insulation between circuits basic installation category III for 400 V v...

Page 17: ...on standard 00 custom made XX Language Polish P English E Acceptance tests without extra requirements 0 with quality inspection certificate 1 with calibration certificate 2 acc to customer s requirements X only after agreement with the manufacturer Code of the highlighted unit Table 7 Code Unit Code Unit 00 without unit 01 V 25 ms 02 A 26 s 03 mV 27 h 04 kV 28 N 05 MV 29 kN 06 mA 30 Pa 07 kA 31 hP...

Page 18: ... h 21 km 45 km h 22 l 46 imp 23 l s XX on request 1 24 l h 1 After consultation with the manufacturer SAMPLE ORDER N20ZPLUS 310100P0 means N20ZPlus meter with voltage input for the 400 V range power supply 85 253 V a c Polish language version version without additional requirements Unit V ...

Page 19: ...N20ZPLUS 09 ...