background image

2

benzine, benzol, butane, ethylene dichlo-

ride, gasoline, hexane, lacquer solvent

vapors, naphtha, natural gas, propane,

propylene, styrene, vinyl acetate, vinyl

chloride, or xylenes.

Group E

: Atmospheres containing combustible metal

dusts regardless of resistivity, or other

combustible dusts of similarly hazardous

characteristics having resistivity of less than

10

5

 ohm/centimeter.

Group F:

Atmospheres containing carbon black,

charcoal, coal,  or  coke  dusts  which  have

more than 8 percent total.

Group G:

Atmospheres containing combustible dusts

having resistivity of 10

5

 ohm/centimeter or

greater.

Description

The heat and smoke actuated detectors are located

in a hazardous location. A Class B two wire detector

circuit extends back to the non-hazardous location

where connections are made to terminals 5 (output

ground) and 1 (output) of the Diode Shunt Barrier

located in the system control panel cabinet (or in a

separate enclosure). Under normal operating condi-

tions voltage and current in the hazardous locations

are at levels known to be safe for intrinsically safe

electrical equipment operating in Group A atmo-

spheres. However, should any combination of two

independent faults occur

 

(plus field wiring failures)

within the system, the barrier will prevent the appear-

ance of excessive voltage and currents in the hazard-

ous location. The ZS-30 module is part of a low

voltage control panel and is connected to the barrier

and detector circuit. The module is mounted on a

System 3 panel along with the control unit. The

intrinsically safe module is interconnected to System 3

modules bus wire cable and draws its power from the

System 3 power supply through the control unit. The

module provides regulated voltage to the detectors in

the hazardous locations through the Diode Shunt

Barrier. It also detects and generates trouble and

alarm conditions. Alarm and trouble conditions are

indicated by red and yellow LEDs on the panel on the

intrinsically safe zone, and corresponding high-going

electronic signals are passed to the control unit. The

detector circuit consists of up to ten DI-3IS ionization-

type smoke detectors or up to five S121 or S122 flame

detectors, in addition to any number of mechanical

(non-energy storing) shorting devices. The detector

circuit is terminated by a 5.6K ohm end of line resistor.

Installation

Refer to Figures 1-3 below when installing the ZS-30.
The Diode Barrier may be located in the main control

panel or in a separate enclosure; but, in either case,

care must be exercised in installation.

System 3 chassis ground must be removed.

 Each

duplicate (redundant) grounding conductor should be

connected to the grounding connections on the barrier

device and run directly to the ground electrode – not

via other paths leading to that electrode.
Each ground wire must be 14 or 18 AWG wire and

should not exceed an impedance of 1 ohm. All ground

wires should be connected separately to the same

ground location. Wiring connected to the barrier output

Figure 1

Field Assembly of Diode Barrier

Summary of Contents for ZS-30

Page 1: ...ties sufficient to produce explosive or ignitable mixtures Class II Class II locations are those that are hazardous because of the presence of combustible dust Class Ill Class Ill locations are those that are hazardous because of the presence of easily ignitable fibers or flyings but in which such fibers or flyings are not likely to be in suspension in the air in quantities sufficient to produce i...

Page 2: ...he barrier and detector circuit The module is mounted on a System 3 panel along with the control unit The intrinsically safe module is interconnected to System 3 modules bus wire cable and draws its power from the System 3 power supply through the control unit The module provides regulated voltage to the detectors in the hazardous locations through the Diode Shunt Barrier It also detects and gener...

Page 3: ...re or in its own enclosure Proper assembly and conduit are essential follow Figure 1 Non energy storing devices such as a manual station may be connected in the detector loop without jeopar Figure 2 Barrier Label dizing the intrinsically safe characteristics of the system Such devices must be connected in parallel with the barrier output must not contain any energy storing component s and must be ...

Page 4: ...S CAN BE USED IN ADDITION TO MECHANICAL NON ENERGY STORING SHORTING DEVICES 5 MAXIMUM SAFE SYSTEM VOLTAGE IS 250 VAC Figure 3 Wiring Diagram ZS 30 Intrinsically Safe Zone P N 315 024056 17 6 REFER TO TEXT FOR LIMITATIONS AND DEFINITION OF THE HAZARDOUS AREA 7 ONLY MECHANICAL NON ENERGY STORING SHORTING DEVICES SUCH AS THE MS 51 MANUAL STATION MAY BE USED 8 WARNING DO NOT MAKE ANY CONNECTION TO TER...

Reviews: