P/N 315-092105-7

Installation Instructions

Model ZCT-8B
Zone Control Telephone Card Module

OPERATION

The Model ZCT-8B Zone Control Telephone
Card from Siemens Industry, Inc. has eight
telephone zones. The name indicates the follow-
ing information:

ZCT – Zone Control Telephone card
8B   – 8 Zone Style Y telephone zone output circuits

The ZCT-8B connects to the telephone riser
through the OMM-1 Output Master module.

All ZCT-8B zone circuits are supervised, pro-
tected, and for Class B (Style Y) zone use only.
The module provides both dial and busy tones.
Up to five telephones can be on line at the same
time.

The ZCT-8B occupies one of eleven
subaddresses of the OCC-1 Output Control Card
module. When installing a zone control module,
use the CSG-M (AccuLINK) configuration print-
out to locate the address of each zone control
card. Use switch S1 to set a unique address for
up to zone control cards as described below.

For additional information on the Voice System,
refer to the MXLV Manual, P/N 315-092036.

INSTALLATION

Remove all system power before installation
first battery and then AC. 
(To power up, con-
nect the AC first and then the battery.)

1. Remove the card from its protective bag.  Do

not touch the gold edge of the board.

2. Refer to the function section of the CSG-M

configuration printout for the address of the
module.

3. Set the card address on switch S1 using

switches SW1 – SW4.
a. Refer to Figure 1 for the location of S1.
b. Refer to Table 1 for switch settings (See

Note below).

Figure 1

ZCT-8B Module Board

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Summary of Contents for ZCT-8B

Page 1: ...uLINK configuration print out to locate the address of each zone control card Use switch S1 to set a unique address for up to zone control cards as described below For additional information on the Voice System refer to the MXLV Manual P N 315 092036 INSTALLATION Remove all system power before installation first battery and then AC To power up con nect the AC first and then the battery 1 Remove th...

Page 2: ...T 8B as shown in Figure 2 See Figure 3 for the exact Figure 2 Placing the Card Slot Key in the OMM 1 Figure 3 Location of User Key for ZCT 8B ELECTRICAL RATINGS 1 79 2 18 FACTORY KEY 1 OMM PIN NUMBERS FACTORY KEY 2 USER KEY 17 20 19 80 location of the key for this module This prevents installation of any other card type in the ZCT 8B slot Two other keys already installed in the OMM 1 prevent rever...

Page 3: ...ed 9 VDC 9mA max Activated 12 5 VDC 300mA max Connect shield to negative zone terminal Figure 4 ZCT 8B Telephone Zone Wiring Diagram NOTES 1 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information 2 Short to Earth Ground on Terminals 1 16 will cause ground fault s t i n U e n o h p e l e T e l b i t a p m o C 1 0 3 T F n o...

Page 4: ...S I S E R S L A N I M R E T E C N A T S I S E R D E R I S E D E S U A C E L B I S S O P M E L B O R P F O 2 o t 1 4 o t 3 6 o t 5 8 o t 7 0 1 o t 9 2 1 o t 1 1 4 1 o t 3 1 6 1 o t 5 1 1 K 0 1 d e t r o h s e n i L n e p o e n i L L O E o N L O E g n o r W s i s s a h c o t 2 2 h g u o r h t 1 g e M 1 g n i r i w n i t r o h S 3 o t 2 5 o t 4 7 o t 6 9 o t 8 1 1 o t 0 1 3 1 o t 2 1 5 1 o t 4 1 g e ...

Reviews: