A24205-A334-B832 (Edition 1)
P/N 315-035600-2
8
WIRING
Remove ELECTRICAL POWER prior to working on equipment
.
All field wiring of the ZAM-180 is connected to the terminal blocks on the
upper side of the ZAM-180.
The screw terminals can accommodate one 12-24 AWG(Ø 0,5mm-2,5mm²)
or two 16-24 AWG, (Ø 0,5mm-1,0mm²).
To connect external wiring
Lift the white cover on the terminal block.
Loosen the screw of the terminal by turning it counterclockwise.
Insert the wire into the side of the terminal block.
Tighten the screw of the terminal block by turning it clockwise
Power Input
24VDC @ 9.5A Max.
Non-Power
Limited Output
24VDC @ 12A
24V
24V
0V
0V
Loc. Audio IN A
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
Back-Up Amp B
Back-Up Amp A
Speaker Line 1A
Speaker Line 1B
Speaker Line 2A
Speaker Line 2B
Loc. Switch A
Earth ground
Earth ground
Loc. Switch B
Loc. Audio IN B
TB1
P5
P4
TB3
ZAM-180
PSC-12
BATTERY
OFF
O —
ON
Figure 12
ZAM-180 Input Power Wiring
NOTES
1. 18AWG
(1,5mm²)
min.
2.
9.5A max. input current
per ZAM-180.
3.