background image

Siemens Industry, Inc.
Building Technologies  Division

A6V10328636_en--_c

7

Cyber security disclaimer

Siemens products and solutions provide security functions to ensure the secure operation of building comfort,
fire safety, security management and physical security systems. The security functions on these products and
solutions are important components of a comprehensive security concept.

It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is
customized to individual security needs. Such a security concept may result in additional site-specific preventive
action to ensure that the building comfort, fire safety, security management or physical security system for your
site are operated in a secure manner. These measures may include, but are not limited to, separating networks,
physically protecting system components, user awareness programs, defense in depth, etc

.

For additional information on building technology security and our offerings, contact your Siemens sales or
project department. We strongly recommend customers to follow our security advisories, which provide infor-
mation on the latest security threats, patches and other mitigation measures.

 

http://www.siemens.com/cert/en/cert-security-advisories.htm

Summary of Contents for XLS-MSE3-ADPT

Page 1: ...3 ADPT The adapter plate installs over the existing studs in an MSE 3 R backbox The inner door has an opening in it for the installation of a FCM2041 U2 U3 operator interface and either one ID MP mounting plate or one ID SP blank plate The inner door is permanently hinged right and is attached to the backbox by screws The XLS MSE3 R ADPT is for indoor use only in dry environments With this convers...

Page 2: ...E TO REINSTALL THE GROUND LUG Figure 1 Installing the XLS MSE3 ADPT Adapter Plate in the MSE 3 Backbox 2 Install the required CC 5 system cardcage PSC 12 power supply and PTB power termination board after careful consideration of NEC Article 760 for separation of power limited and non powered limited wiring Refer to Figure 2 Use the hardware provided with those modules to mount them to the adapter...

Page 3: ...e top and bottom holes on the right hand side of the backbox 2 Tighten the screws just a few turns leaving a 1 8 inch gap between the head of the screws and the backbox 3 Slide the inner door into position under the screws 4 Make certain the flange at the left hand top of the inner door is seated in the lip in the backbox Refer to Figure 3 Adjust the door as needed so that it seats securely in the...

Page 4: ...r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w P S D I e h t s a e z i s e m a s e h t t r e s n i k n a l B t e k c a r b e t a l p g n i t n u o m P M D I d e r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w XLS MSE3 ADPT INNER DOOR ID SP OR ID MP MOUNTING FCM2041 U2 U3 MOUNTING Figure 4 Inner Door Modules Install the Outer Door The out...

Page 5: ...limited field wiring the installer must comply with NEC article 760 which states The fire alarm power limited circuits are installed usingTypes FPL FPLR FPLP or permitted substitute cable provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 35 mm or by a noncon ductive sleeve or nonconductive barrier from all other conductors If energy l...

Page 6: ...wer limited wiring Use the existing lances on the adapter plate to dress the wires as needed to main tain separation of power limited and non power limited wiring Install Wiring The primary mains input must have a separate or dedicated circuit breaker Wire in accordance with local codes and Article 760 of NEC 1 Remove the knockouts in the backbox for the entry of field wiring 2 Pull all field wiri...

Page 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...