Siemens XLS-MSE3-ADPT Installation Instructions Manual Download Page 5

Siemens Industry, Inc.
Building Technologies  Division

A6V10328636_en--_c

5

   

MSE-3 BACKBOX

OUTER DOOR

GROUND WIRE

WIRE: 12AWG

UNUSED STUD

Figure 5

Ground Wire Installation

WIRING

In compliance with NEC Article 760,  all power limited fire protective signaling
conductors must be separated a minimum of ¼ inch from all of the following wiring
located within a control panel:

electric light

power

Class 1 or non-power limited fire protective signaling conductors

To meet these requirements, the following guidelines 

must be observed

 when

installing modules and wiring to this control panel.

When installing power limited field wiring, the installer must comply with NEC article
760, which states:

The fire alarm power-limited circuits are installed using Types FPL, FPLR, FPLP or
permitted substitute cable, provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in. (6.35 mm) or by a noncon-
ductive sleeve or nonconductive barrier from all other conductors.

If energy limited cable or equivalent is not used within the enclosure,  then the following
guidelines do not apply. In that case, be sure to follow standard wiring     practices.

Wiring Entering Enclosure

Non-Power Limited Wiring

Wiring entering the enclosure from the bottom and right side of the backbox is
considered non-power limited wiring. Wiring must be in the shortest route and must
not overlap any other wiring.

Summary of Contents for XLS-MSE3-ADPT

Page 1: ...3 ADPT The adapter plate installs over the existing studs in an MSE 3 R backbox The inner door has an opening in it for the installation of a FCM2041 U2 U3 operator interface and either one ID MP mounting plate or one ID SP blank plate The inner door is permanently hinged right and is attached to the backbox by screws The XLS MSE3 R ADPT is for indoor use only in dry environments With this convers...

Page 2: ...E TO REINSTALL THE GROUND LUG Figure 1 Installing the XLS MSE3 ADPT Adapter Plate in the MSE 3 Backbox 2 Install the required CC 5 system cardcage PSC 12 power supply and PTB power termination board after careful consideration of NEC Article 760 for separation of power limited and non powered limited wiring Refer to Figure 2 Use the hardware provided with those modules to mount them to the adapter...

Page 3: ...e top and bottom holes on the right hand side of the backbox 2 Tighten the screws just a few turns leaving a 1 8 inch gap between the head of the screws and the backbox 3 Slide the inner door into position under the screws 4 Make certain the flange at the left hand top of the inner door is seated in the lip in the backbox Refer to Figure 3 Adjust the door as needed so that it seats securely in the...

Page 4: ...r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w P S D I e h t s a e z i s e m a s e h t t r e s n i k n a l B t e k c a r b e t a l p g n i t n u o m P M D I d e r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w XLS MSE3 ADPT INNER DOOR ID SP OR ID MP MOUNTING FCM2041 U2 U3 MOUNTING Figure 4 Inner Door Modules Install the Outer Door The out...

Page 5: ...limited field wiring the installer must comply with NEC article 760 which states The fire alarm power limited circuits are installed usingTypes FPL FPLR FPLP or permitted substitute cable provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 35 mm or by a noncon ductive sleeve or nonconductive barrier from all other conductors If energy l...

Page 6: ...wer limited wiring Use the existing lances on the adapter plate to dress the wires as needed to main tain separation of power limited and non power limited wiring Install Wiring The primary mains input must have a separate or dedicated circuit breaker Wire in accordance with local codes and Article 760 of NEC 1 Remove the knockouts in the backbox for the entry of field wiring 2 Pull all field wiri...

Page 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 8: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V10328636_en _c P N A5Q00054384 ...

Reviews: