INTRODUCTION

Use the Model XLS-MSE3(R)-ADPT Adapter Kit from Siemens Industry, Inc., to
upgrade existing MXL-IQ Systems installed in Model MSE-3L(R) or MSE-3M(R)
backboxes to FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
Systems. The MSE-3L(R) and MSE-3M(R) will be referred to as MSE-3(R) in the
remainder of the document.

The XLS-MSE3(R)-ADPT Adapter Kit consists of an adapter plate, inner door and outer
door.  The XLS-MSE3-ADPT (S54430-C14-A1) inner and outer doors are black; the
XLS-MSE3R-ADPT (S54430-C14-A2) inner door is black and outer door is red. The
XLS-MSE3-ADPT and the XLS-MSE3R-ADPT are identical in all other ways and will be
referred to in the remainder of this document as XLS-MSE3-ADPT.

The adapter plate installs over the existing studs in an MSE-3(R) backbox. The inner
door has an opening in it for the installation of a FCM2041-U2/-U3 operator interface
and either one ID-MP mounting plate or one ID-SP blank plate.  The inner door is
permanently hinged right and is attached to the backbox by screws.

The XLS-MSE3(R)-ADPT is for indoor use only in dry environments.

With this conversion, the maximum battery set that can be used in the backbox is 18

AH (model BP-61). If larger batteries are required, use either a BB-55 or CAB-BATT

battery box.

To convert an MSE-3(R) backbox from an MXL-IQ System to an XLS/Desigo Fire
Safety Modular/Cerberus PRO Modular component system, you must first disas-
semble the MXL-IQ and then assemble the XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular.  This two-part procedure is described in detail below.

DISASSEMBLY OF MXL-IQ SYSTEM

Remove all system power, first battery and then AC.

1.

Remove and discard the outer door. Reserve the hardware used to secure it
in place.

2.

Disconnect and remove the modules from the inner door.

3.

Remove all modules from the backbox, making sure to mark all wires.
Reserve the hardware used to secure them in place.

4.

Remove the MPS power supply and batteries from the backbox.

Summary of Contents for XLS-MSE3-ADPT

Page 1: ...3 ADPT The adapter plate installs over the existing studs in an MSE 3 R backbox The inner door has an opening in it for the installation of a FCM2041 U2 U3 operator interface and either one ID MP mounting plate or one ID SP blank plate The inner door is permanently hinged right and is attached to the backbox by screws The XLS MSE3 R ADPT is for indoor use only in dry environments With this convers...

Page 2: ...E TO REINSTALL THE GROUND LUG Figure 1 Installing the XLS MSE3 ADPT Adapter Plate in the MSE 3 Backbox 2 Install the required CC 5 system cardcage PSC 12 power supply and PTB power termination board after careful consideration of NEC Article 760 for separation of power limited and non powered limited wiring Refer to Figure 2 Use the hardware provided with those modules to mount them to the adapter...

Page 3: ...e top and bottom holes on the right hand side of the backbox 2 Tighten the screws just a few turns leaving a 1 8 inch gap between the head of the screws and the backbox 3 Slide the inner door into position under the screws 4 Make certain the flange at the left hand top of the inner door is seated in the lip in the backbox Refer to Figure 3 Adjust the door as needed so that it seats securely in the...

Page 4: ...r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w P S D I e h t s a e z i s e m a s e h t t r e s n i k n a l B t e k c a r b e t a l p g n i t n u o m P M D I d e r u c e S r o o d n i s d u t s n o s t n u o M s t u n 2 3 0 1 o w t h t i w XLS MSE3 ADPT INNER DOOR ID SP OR ID MP MOUNTING FCM2041 U2 U3 MOUNTING Figure 4 Inner Door Modules Install the Outer Door The out...

Page 5: ...limited field wiring the installer must comply with NEC article 760 which states The fire alarm power limited circuits are installed usingTypes FPL FPLR FPLP or permitted substitute cable provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 35 mm or by a noncon ductive sleeve or nonconductive barrier from all other conductors If energy l...

Page 6: ...wer limited wiring Use the existing lances on the adapter plate to dress the wires as needed to main tain separation of power limited and non power limited wiring Install Wiring The primary mains input must have a separate or dedicated circuit breaker Wire in accordance with local codes and Article 760 of NEC 1 Remove the knockouts in the backbox for the entry of field wiring 2 Pull all field wiri...

Page 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 8: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V10328636_en _c P N A5Q00054384 ...

Reviews: