Plant type
Maximum
distance
Total cable
length
Cable cross-
section
Number of
devices (slaves)
Max.
transmission rate
Small
developments
1000 m
4000 m
0.8 mm
2
64
2400 baud
Large
developments
3000 m*
5000 m
1.5 mm
2
64
2400 baud
Direct vicinity
5000 m*
7000 m
1.5 mm
2
16
300 baud
Point-to-point
connection
10000 m*
10000 m
1.5 mm
2
1
300 baud
* Shielded cabling required at a distance in excess of 1000 m
(see EN13757-2 appendix E).
Signal specification
M-bus
Condition
Minimum
Typical
Maximum Measuring unit
Number of unit M-bus loads per
web server
WTV676-HB6035
0
-
20
-
Transfer rate
C
Segment
≤ 382 nF
300
2400
9600
baud
Bus power
WTV676-HB6035
24
40
42
R
Bus current
WTV676-HB6035
0
30
mA
Connection terminals
The device has the following connection terminals / LED
A
B
C
E
G
F
H
I
D
WTV676-HB6035
A
Ethernet connection
B
USB connection (no function)
C
Antenna connection
D
Terminals (4) and (5): Connections
M1 and M2 for M-bus devices and
the following level converters.
Terminals (1), (2) and (3) are not
used.
Do not apply electricity to these
terminals.
E
Terminals (16) and (17): Power
supply AC/DC 24 V
F
Terminals (12) and (13): Relay
connections for digital output 1, max.
AC/DC 30 V
G
Terminals (14) and (15): Relay
connections for digital output 2, max.
AC/DC 30 V
H
Terminals (9), (10), and (11):
Connections for the digital inputs.
Terminal (8): Reference for digital
inputs
I
Terminals (6) and (7) are not used.
Do not apply electricity to these
terminals.