8
A5E00817847-01
Operating Instructions
English
Rated current of
frame size I
mn
Rated
current I
n
I
r
, current settings of long-time
delay protection 40 °C
Instantaneous short circuit protection I
i
For power distribution
protection
For motor protection
A/B/C phase
N pole
A/B/C phase
N pole
A/B/C phase
N pole
63 A
10 A
10 A
10 A
500 A
500 A
500 A
500 A
16 A
16 A
16 A
500 A
500 A
500 A
500 A
20 A
20 A
20 A
500 A
500 A
500 A
500 A
25 A
25 A
25 A
500 A
500 A
500 A
500 A
32 A
32 A
32 A
500 A
500 A
500 A
500 A
40 A
40 A
40 A
500 A
500 A
500 A
500 A
50 A
50 A
50 A
500 A
500 A
500 A
500 A
63 A
63 A
63 A
630 A
630 A
756 A
756 A
100 A
32 A
32 A
32 A
500 A
500 A
500 A
500 A
40 A
40 A
40 A
500 A
500 A
500 A
500 A
50 A
50 A
50 A
500 A
500 A
500 A
500 A
63 A
63 A
63 A
630 A
630 A
756 A
756 A
80 A
80 A
80 A
800 A
800 A
960 A
960 A
100 A
100 A
100 A
1000 A
1000 A
1200 A
1200 A
(19) Tripping characteristic curves for VT63 / VT100 circuit breakers
VT63
VT100
Up to 40 A
From 63 A
(18)