background image

KIT INSTALLATION INSTRUCTION

Siemens Industry, Inc.

 

 

 

Kit P/N 16300-1355

 

15900-378 

Kit P/N TGX:16300-1438

 

Rev. 8 
November 2021 

 

ValvePAC

™ Series 760 Valve Positioner 

I/P Transducer Kit 

 
Use this kit to convert a Model 760P pneumatic input valve positioner to a Model 760E that accepts a 4-20 mA input 
signal. This kit is also used to replace a failed I/P transducer in a 760E. A copy of SD760, the Series 760 Installation 
and Service Instruction, should be available for reference. Refer to SD760 for non-hazardous and hazardous area 
installation requirements and for environmental specifications. When installing or servicing in a hazardous area, 
refer to Siemens Control Drawing 15032-7602, supplied in SD760. 
 
 

 

WARNING

 

 

 

 

Electrical shock hazard 

Explosion hazard 

 

Can cause death, serious injury or property damage 

 

Remove power from all wires and terminals before working on 
equipment. 

 

In potentially hazardous atmosphere, remove power from equipment 
before connecting or disconnecting power, signal, or other circuit. 

 

Observe all pertinent regulations regarding installation in a hazardous 
area.

 

 

 

 

Kit Parts List 

Description 

Quantity 

Description 

Quantity 

I/P Transducer 

10-32 x 3/8 Slotted Hex Head Screw 

I/P Manifold 

8-32 x 1/4 Binding Head Screw 

O-Ring 

8-32 x .375 SL/TX PN TR 

Wire Clamp 

#8 External Tooth Lockwasher 

Clamping Plate 

Terminal Washer 

10-32 x 2-1/4 Binding Head Screw 

Pipe Plug 

 

Installation 

Perform the following steps to install the parts in this kit. Note the following when a step is prefaced with a 760 
model: 

 

“760P” - Perform this step when converting a 760P to a 760E. 

 

“760E” - Perform this step when replacing an I/P transducer in a 760E. 

1.

 

Remove all electrical power and process signals from the positioner. 

2.

 

Remove supply air from the positioner. 

3.

 

Remove the cover by loosening a screw at each corner of the cover and lifting the cover from the positioner. 

Summary of Contents for ValvePAC Series

Page 1: ...inals before working on equipment In potentially hazardous atmosphere remove power from equipment before connecting or disconnecting power signal or other circuit Observe all pertinent regulations regarding installation in a hazardous area Kit Parts List Description Quantity Description Quantity I P Transducer 1 10 32 x 3 8 Slotted Hex Head Screw 1 I P Manifold 1 8 32 x 1 4 Binding Head Screw 1 O ...

Page 2: ...end 22 AWG shielded twisted pair wire to the and connections of the I P transducer terminal strip Connect the shield to the ground screw inside the positioner The wires should enter the positioner through the conduit connection and be routed through the wire clamp see the figure Tighten the wire clamp mounting screw as needed 11 Verify I P operation and positioner calibration Refer to Section 4 Ca...

Page 3: ...ntation or software Online Support Request http www siemens com automation support request Technical Support 1 800 333 7421 8 a m to 4 45 p m eastern time Monday through Friday except holidays Customer Service Returns 1 800 365 8766 warranty and non warranty Public Internet Site http www usa siemens com pi Technical Publications in PDF Click the above link to go to the Siemens Internet site and th...

Page 4: ...ames of Siemens Industry Inc or other supplier companies whose use by third parties for their own purposes could violate the rights of the owners Siemens Industry Inc assumes no liability for errors or omissions in this document or for the application and use of information in this document The information herein is subject to change without notice Procedures in this document have been reviewed fo...

Reviews: