™ Series 760 Valve Positioner
I/P Transducer Kit
Use this kit to convert a Model 760P pneumatic input valve positioner to a Model 760E that accepts a 4-20 mA input
signal. This kit is also used to replace a failed I/P transducer in a 760E. A copy of SD760, the Series 760 Installation
and Service Instruction, should be available for reference. Refer to SD760 for non-hazardous and hazardous area
installation requirements and for environmental specifications. When installing or servicing in a hazardous area,
refer to Siemens Control Drawing 15032-7602, supplied in SD760.
WARNING
Electrical shock hazard
Explosion hazard
Can cause death, serious injury or property damage
•
Remove power from all wires and terminals before working on
equipment.
•
In potentially hazardous atmosphere, remove power from equipment
before connecting or disconnecting power, signal, or other circuit.
•
Observe all pertinent regulations regarding installation in a hazardous
area.
Kit Parts List
Description
Quantity
Description
Quantity
I/P Transducer
1
10-32 x 3/8 Slotted Hex Head Screw
1
I/P Manifold
1
8-32 x 1/4 Binding Head Screw
1
O-Ring
4
8-32 x .375 SL/TX PN TR
1
Wire Clamp
1
#8 External Tooth Lockwasher
1
Clamping Plate
1
Terminal Washer
1
10-32 x 2-1/4 Binding Head Screw
1
Pipe Plug
1
Installation
Perform the following steps to install the parts in this kit. Note the following when a step is prefaced with a 760
model:
•
“760P” - Perform this step when converting a 760P to a 760E.
•
“760E” - Perform this step when replacing an I/P transducer in a 760E.
1.
Remove all electrical power and process signals from the positioner.
2.
Remove supply air from the positioner.
3.
Remove the cover by loosening a screw at each corner of the cover and lifting the cover from the positioner.