background image

 

GAMMA 

instabus

 

Technical Specification 

 March 2010 

Colour touch panel UP 588/13 

5WG1 588-2AB13 

Colour touch panel UP 588/23 

5WG1 588-2AB23 

 

 
Accessories: 
Design frame aluminium  

5WG1 588-8AB12 

Design frame stainless steel design 

5WG1 588-8AB13 

Design frame glass black 

5WG1 588-8AB14 

Design frame glass white 

5WG1 588-8AB15 

 

flush-type box 

5WG1 588-8EB01 

 

Siemens AG 

UP 588, 6 pages 

Technical Manual 

Industry Sector, Building Technologies 

Low Voltage Distribution 

© Siemens AG 2010 

Update: http://www.siemens.com/gamma 

PO Box 10 09 53, D-93009 Regensburg 

Subject to change without further notice 

 

 

2.3.1.7/3 

 

Dimensions of corresponding flush-type box (W × H × 
D): 161.5 × 135 × 64 mm, not included with supply 

 

Weight: approx. 510 g 

 

Electrical safety 

 

Degree of pollution: 

 

 

  2 

 

Type of protection (according to EN 60529): IP20 

 

Protection class (to IEC 1140):         

   I 

 

Overvoltage category:    

 

   III 

 

Bus: safety extra-low voltage SELV 24V DC 

 

Device complies with EN50090-2-2 

 

EMC requirements 

Complies with EN 61000-6-3, EN 61000-6-2 and EN 
50090-2-2 
 

Ambient conditions 

 

Climatic withstand capability: EN 50090-2-2 

 

Ambient operating conditions: 0°C to +45°C 

 

Storage temperature: -25°C to +70°C 

 

Relative humidity (non-condensing): 5% to 93% 

 

Markings 

KNX/EIB  
 

EC mark 

In accordance with the EMC guideline (residential and 
functional buildings) and the low voltage guideline 
 

Location and function of the conjunction- and 

operating elements  

 
The device connections as well as the programming 
button and programming LED which are required for the 
commissioning stage are accessible at the back of the 

device. Figure 2 shows the back of the device. 

C

D

B

A

 

Figure 2:

 Location of the connection and operating 

elements 

 

 

A   

   Connection terminal 230 V or 24 V AC/DC 

B

      Programming LED 

C  

    Programming button 

D

      Bus terminal 

 

Figure 3:

 Mounting the touch panel

 

 

1 Flush-type 

box 

Colour touch panel 

3 Fixing 

screws 

different design frames 

5 Passepartout 

blind 

1

 

2

 

3

 

4

5

Summary of Contents for UP 588/13

Page 1: ...efore function as the master timer in a KNX system Via the system settings one of four different design templates can be selected for the display and operator interface The following accessories are needed for the colour touch panel Design frame aluminium 5WG1 588 8AB12 Design frame stainless steel design 5WG1 588 8AB13 Design frame glass black 5WG1 588 8AB14 Design frame glass white 5WG1 588 8AB1...

Page 2: ...power supply For planning and construction of electric installations the relevant guidelines regulations and standards of the respective country are to be considered Technical specifications Power supplies Bus voltage via the bus line External power supply for Colour Touch panel UP 588 13 230 V AC 10 50 60 Hz Colour Touch panel UP 588 23 18 36 V DC 400 mA base isolated comp 230 V 14 28 V AC 400 mA...

Page 3: ...ory III Bus safety extra low voltage SELV 24V DC Device complies with EN50090 2 2 EMC requirements Complies with EN 61000 6 3 EN 61000 6 2 and EN 50090 2 2 Ambient conditions Climatic withstand capability EN 50090 2 2 Ambient operating conditions 0 C to 45 C Storage temperature 25 C to 70 C Relative humidity non condensing 5 to 93 Markings KNX EIB EC mark In accordance with the EMC guideline resid...

Page 4: ... power supply cables must not be fed into the flush type box through the same recess Inside the box the cable is to be routed so that there is a guaranteed separation of at least 10 mm between bus and power supply cables Connecting the bus cable figure 4 A The bus terminal C3 is suitable for solid conductors with a diameter of 0 6 0 8 mm Strip off approx 3 cm of the bus cable insulation Strip the ...

Page 5: ...val can be made easier by lifting the power supply connection terminal C4 slightly with a flat bladed screwdriver To do this push the blade of the screwdriver into the centre of the terminal detente between the power supply connection terminal C4 and the base of the slot Removing the bus terminal figure 4 A The bus terminal C3 is in the left slot It consists of two parts C3 2 and C3 3 each with fo...

Page 6: ...the touch panel It has a length of 1 m and have a transfer rate of 480 MBit sec After completing the transfer remove the cable and mount the design frame as described above Care instructions The display s design frame and plastic surface can be cleaned with off the shelf solvent free cleaning agents The display surface itself should be cleaned with a soft damp cloth e g spectacles cloth and if nec...