background image

GAMMA 

instabus

 

Technical Specification 

March 2010 

Colour touch panel UP 588/13 

5WG1 588-2AB13 

Colour touch panel UP 588/23 

5WG1 588-2AB23 

 

 
Accessories: 
Design frame aluminium  

5WG1 588-8AB12 

Design frame stainless steel design 

5WG1 588-8AB13 

Design frame glass black 

5WG1 588-8AB14 

Design frame glass white 

5WG1 588-8AB15 

 

flush-type box 

5WG1 588-8EB01 

 

Technical Manual 

UP 588, 6 pages 

Siemens AG

 

 

 

Industry Sector, Building Technologies 

Update: http://www.siemens.com/gamma 

© Siemens AG 2010 

Low Voltage Distribution

 

 

Subject to change without further notice 

PO Box 10 09 53, D-93009 Regensburg 

2.3.1.7/2

 

 

The depth of the recess must be at least 64 mm. 

 
 

 

 

Figure 1: 

Drilling jig for cavity wall box Colour  

 

       

touchpanel UP 588 

 

V

 

DANGER 

 

The device may only be installed and commissioned by 
an authorised electrician. 

 

The device may only be used in connection with the 
named accessories, in particular the flush-type box. 

 

230V devices which are not included with supply may 
not be inserted in the flush-type box. It is also not 
possible to loop through 230V cables. 

 

The prevailing safety and accident regulations should 
be observed. 

 

The power supply voltage may only be connected to 
the supply if the device has been fully installed. 

 

Protective isolation should be ensured between the 
bus cable and the 230V power supply. 

 

For planning and construction of electric installations, 
the relevant guidelines, regulations and standards of 
the respective country are to be considered. 

 
 

 

 

 

 

 

 

Technical specifications 

 

Power supplies 

 

Bus voltage: via the bus line 

 

External power supply for:  

 

Colour Touch panel UP 588/13 
230 V AC ±10%, 50/60 Hz 

 

Colour Touch panel UP 588/23 
18 – 36 V DC, 400 mA,  base isolated comp. 230 V   
14 – 28 V AC, 400 mA,  base isolated comp. 230 V  

 

Operating elements 

 

Programming button to toggle between normal and 
addressing modes 

 

Reset button to reset the device 

 

Resistive analogue touch with contact-sensitive area on 
the display 

 

Display elements 

 

Red programming LED for displaying normal/addressing 
mode 

 

Graphics-capable TFT colour display 320 × 240 pixels 
(1/4 VGA) with LED background lighting 

 

Display fault like ISO 13406-2 fault league 3 by error 
type 1 and error type 2 

 

Connections 

 

Bus line: KNX bus terminal, screwless 
0.6... 0.8 mm 

 solid, stripped length 5 mm. 

 

USB socket mini typ B (use only if needed for image  
and symbols load) 

 

Power supply  
stripped length: 6...7 mm 
The following conductor/conductor cross-sections are 
permitted: 

-

 

0.5...2.5 mm

2

 solid 

-

 

0.5..0.1.5 mm

2

 finely-stranded 

 

Mechanical data 

 

Housing: Touch panel: plastic   

 

Outer dimensions of the display modul (W x H x D):  
157 x 131 x 60 mm 

 

Outer dimensions of the design frames (W × H × D):   
194 × 156 × 5 mm 

 

Outer dimensions of the passepartout blind (W × H): 
152 × 123 mm 

 

Mounting depth in flash-type box: 64 mm 

 

Installation: is screwed into the corresponding flush-
type box 

Summary of Contents for UP 588/13

Page 1: ...efore function as the master timer in a KNX system Via the system settings one of four different design templates can be selected for the display and operator interface The following accessories are needed for the colour touch panel Design frame aluminium 5WG1 588 8AB12 Design frame stainless steel design 5WG1 588 8AB13 Design frame glass black 5WG1 588 8AB14 Design frame glass white 5WG1 588 8AB1...

Page 2: ...power supply For planning and construction of electric installations the relevant guidelines regulations and standards of the respective country are to be considered Technical specifications Power supplies Bus voltage via the bus line External power supply for Colour Touch panel UP 588 13 230 V AC 10 50 60 Hz Colour Touch panel UP 588 23 18 36 V DC 400 mA base isolated comp 230 V 14 28 V AC 400 mA...

Page 3: ...ory III Bus safety extra low voltage SELV 24V DC Device complies with EN50090 2 2 EMC requirements Complies with EN 61000 6 3 EN 61000 6 2 and EN 50090 2 2 Ambient conditions Climatic withstand capability EN 50090 2 2 Ambient operating conditions 0 C to 45 C Storage temperature 25 C to 70 C Relative humidity non condensing 5 to 93 Markings KNX EIB EC mark In accordance with the EMC guideline resid...

Page 4: ... power supply cables must not be fed into the flush type box through the same recess Inside the box the cable is to be routed so that there is a guaranteed separation of at least 10 mm between bus and power supply cables Connecting the bus cable figure 4 A The bus terminal C3 is suitable for solid conductors with a diameter of 0 6 0 8 mm Strip off approx 3 cm of the bus cable insulation Strip the ...

Page 5: ...val can be made easier by lifting the power supply connection terminal C4 slightly with a flat bladed screwdriver To do this push the blade of the screwdriver into the centre of the terminal detente between the power supply connection terminal C4 and the base of the slot Removing the bus terminal figure 4 A The bus terminal C3 is in the left slot It consists of two parts C3 2 and C3 3 each with fo...

Page 6: ...the touch panel It has a length of 1 m and have a transfer rate of 480 MBit sec After completing the transfer remove the cable and mount the design frame as described above Care instructions The display s design frame and plastic surface can be cleaned with off the shelf solvent free cleaning agents The display surface itself should be cleaned with a soft damp cloth e g spectacles cloth and if nec...