Technical product information 

February 2012 

UP 258D11 OPTISENS OFFICE Presence detector / motion detector with lighting control 

5WG1 258 2DB11 

 

Siemens AG 

UP 258D11, 8 pages 

Technical manual 

Infrastructure & Cities Sector, Building Technologies 
Control Products and Systems 

© Siemens AG 2012 

Update: http://www.siemens.com/gamma 

P.O. Box 10 09 53, D 93009 Regensburg 

Subject to change without further notice 

 

 

2.13.1.6/3 

Application program 

25 CO Presence detector with light control   910501 
 
The following features are integrated in the device: 

 

Brightness measurement as mixed light measurement; 
Calibration via bus 

 

Integrated 2 point brightness controller (switching) 

 

Presence and motion detection 

 

Operation as an individual sensor or as the main or 
ancillary sensor for covering wider areas. 

 

Separate output (as a KNX   object) for heating, ventila
tion and air conditioning applications. 

 

Selectable functions for presence, motion, and HVAC 
detector function blocks: 

 Switching On/Off 
 8 bit value (0...255) 
 16 bit value (0...65535) 
 16 bit value (temperature) (0°C – 40°C) 
 16 bit value (brightness) (0 – 2000Lux) 
 8 bit scene 

 

Integrated IR receiver for a IR remote control (see ac
cessories) 

 

Selectable functions per IR pair of pushbuttons: 

 Switching On/Off/toggle 
 8 bit value (0...255) 
 16 bit value (0...65535) 
 16 bit value(temperature) (0°C – 40°C) 
 16 bit value (brightness) (0 – 2000Lux) 
 8 bit scene 

 
The KNX Engineering Tool Software (ETS) version 3.0 f is 
required to load the application program. 
 
 
 

Installation notes 

 
 

V

V

V

V

 

DANGER 

 

The device must be mounted and commissioned by an 
authorized electrician. 

 

When connecting the device, it should be ensured that 
the device can be isolated. 

 

The device must not be opened. 

 

For planning and  construction  of  electric installations, 
the  relevant  guidelines,  regulations  and  standards  of 
the respective country are to be considered. 

 
 
 
 
 

Technical data 

 

Power supply 

 

via bus line 

 

Current drain approx. 10 mA 

 

Presence detection 

 

Type:  Passive infrared (PIR) 

 

Range:  

 

horizontal 360°, vertical ca. 100°,  
for monitoring of an area of 3 x 3 m up to  approx. 
5 x 5 m (dependent on the mounting resp. ceiling 
height) 

 

 

 

Brightness measurement 

 

Type:   Mixed light measurement 

 

Measuring range: 20...1000 Lux 

 

IR receiver 

For remote control (see accessories)

 

max. Distance detector <–> remote control:  ~ 4.5 m 

 

Operating elements 

 

1 commissioning push button: 
for toggling between normal mode / addressing mode 

 

for  reset the device to the default factory settings and 
to activate manufacturer specific functions 

 

Display elements 

 

1 red LED: for checking the bus voltage and for display
ing normal mode / addressing mode 

 

This LED indicated also the reset to the default factory 
settings  and further activated manufacturer specific 
functions. 

 

This LED also indicates presence / motion detection in 
test mode . 

 

Connections 

 

KNX bus line: bus terminal block 

 

Mechanical specifications 

 

Housing: plastic  

 

Dimensions (DxT):  

;

 53 mm x 31 mm (without design cover) 

;

 88 mm x 63 mm (with design cover) 

 

Weight:  approx. 70g 

Summary of Contents for UP 258D11 OPTISENS OFFICE

Page 1: ...ach functional block motion detector presence detector HVAC detector via corresponding parameters Each time a presence is detected the overshoot time is started Its duration is separately configurable for each functional block The end of presence is determined by the end of the overshoot time The duration of the dead time is also configurable per functional block It is used to protect the actuator...

Page 2: ... to control other devices The IR decoder can be controlled only with one of the Siemens IR remote controls shown in figure 1 The re mote controls have a range of 5 meters maximum The IR decoder cannot distinguish between remote con trols The functionality of button pairs A to F see dia gram in figure 1 will be configured via the ETS Figure 1 IR remote control units for UP 258D11 Commissioning Fact...

Page 3: ... Engineering Tool Software ETS version 3 0 f is required to load the application program Installation notes V V V V DANGER The device must be mounted and commissioned by an authorized electrician When connecting the device it should be ensured that the device can be isolated The device must not be opened For planning and construction of electric installations the relevant guidelines regulations an...

Page 4: ...ording to IEC 60664 1 III Bus safety extra low voltage SELV DC 24 V Device complies with EN 60669 2 1 EMC requirements Complies with EN 50428 Environmental conditions Climatic withstand capability EN 50090 2 2 Ambient operating temperature 5 45 C Storage temperature 20 70 C Relative humidity not condensing 5 to 93 Reliability Failure rate 410 fit at 40 C Markings KNX EIB CE mark In accordance with...

Page 5: ...g Basics The PIR sensor reacts to temperature differences The lower the temperature difference between the ambient temperature and the moving object the less sensitive the analysis In other words moving objects will not then be detected as efficiently and the catch ment area is restricted Note There must be an unobstructed line of sight to the person in the catchment area People behind walls etc i...

Page 6: ...ews E1 UP 258D device E2 Socket fixing screws E3 UP socket Depth min 40 mm 60 mm E4 Additional fixing holes offset by 90 Mounting the fixing clamps for mounting the device in suspended ceilings Extend the fixing claws slightly and push over the lugs on the UP 258D Figure 6 Mounting the fixing clamps for mounting the device in suspended ceilings G1 UP 258D device G2 Fixing clamp Installation in sus...

Page 7: ... protec tion for the tilting sensor head It can be removed before mounting the detector Separate the snaplock hooks on the shade with a screw driver and fold the shade down If you want to constrain the detection area you can cut out the shade The shade can be clipped back on if need after mounting the detector Figure 9 Mounting Dismounting the shade K1 UP 258D device K2 Shade K3 Screwdriver Cuttin...

Page 8: ... Ac cordingly be gentle while working Figure 12 Dismounting the design cover N1 UP 258D device N2 Design cover N3 Screwdriver caution Dimension drawing Dimensions in mm General notes The operating instructions must be handed over to the client Any faulty device is to be sent together with a return delivery note of the local Siemens office If you have further questions concerning the product please...

Reviews: