UP 258D11 OPTISENS OFFICE Presence detector / motion detector with lighting control 

5WG1 258 2DB11 

  

Technical manual 

UP 258D11, 8 pages 

Siemens AG  

 

 

Infrastructure & Cities Sector, Building Technologies 

Update: http://www.siemens.com/gamma 

© Siemens AG 2012 

Control Products and Systems 

 

Subject to change without further notice 

P.O. Box 10 09 53, D 93009 Regensburg 

2.13.1.6/2 

brightness  fluctuations  are  filtered  out.  The  measure
ment  range  of  the  internal  light  sensor  is  between  20 
and 1000 lux. 
The  settings  determine  whether  the  brightness  value 
computed  by  the  device  or  a  brightness  value  received 
from  outside  is  used  for  the  detector's  remaining  func
tional blocks. 
 

Integrated light control (on – off) 

If the brightness controller is enabled (automatic mode) 
the lighting is switched on as soon as the brightness falls 
below a set lower threshold. The lighting is switched off 
if  the  set  upper  brightness  threshold  is  exceeded.  The 
brightness  thresholds  are  variable  either  via  parameters 
or via communication objects. 
The  controller  can  also  be  operated  semi automatically 
by  separating  into  two  individual  switching  objects  for 
exceeding  or  falling  below  the  threshold.  In  this  way,  it 
can be switched to “Only on” or “Only off.” 
If  the  controller  receives  a  switching  or  dimming  com
mand  via  the  associated  communication  object  over 
KNX/EIB,  then  this  is  deemed  an  external  override  and 
the controller switches automatic mode off. This change 
of  status  is  sent  simultaneously  on  the  bus  via  the 
“Automatic Status” object. 
 

Operation via infrared (IR) remote control 

The  IR  receiver  integrated  in  the  presence  detector  can 
control  light  and  shade,  as  well  as  store  and  call  up 
scenes via a special IR remote control. 
The  IR  commands  implemented  can  be  combined  via 
communication objects with the other function blocks or 
used to control other devices. 
The  IR  decoder  can  be  controlled  only  with  one  of  the 
Siemens  IR  remote  controls  shown  in  figure 1.  The  re
mote controls have a range of 5 meters maximum. 
The IR decoder cannot distinguish between remote con
trols.  The  functionality  of  button  pairs  A  to  F  (see  dia
gram in figure 1) will be configured via the ETS. 

 

Figure 1. IR remote control units for UP 258D11 
 

Commissioning / Factory default settings 

 
After  the  device  is  connected  to  the  bus  voltage,  the 
sensor  must  first  "Restart".  In  this  phase,  the  program
ming  LED  flashes  double.(

¼sec.  ON 

  ¼sec.  OFF 

 

¼sec. ON 

 1¼sec. OFF 

)

 

 After "Restart" of the sensor, it appears that no motion is 
detected at present, the programming LED is off. 
 

Factory default settings 

In the as delivered state, the parameter Operating Mode 
is set to Setting Mode. 
While  the  device  is  in  "Setting  Mode",  the  integrated 
programming  LED  displays  the  PIR  sensor  state.  (illumi
nates briefly with motion) 
 
Note: 
The  programming  LED  can  be  recognized  more  easily 
without the design cover! 
 
If  the device is in programming mode,  the  LED  stays  on 
and does not flash. The PIR state is then not displayed. 
 

Programming mode 

Press  the  programming  key  short  (<  0,5  s)  to  enable 
programming  mode.  This  is  indicated  by  the  program
ming LED. 
 

Factory setting 

When the programming key is pressed very long (> 20 s) 
the device is reset to the default factory settings. This is 
indicated  by  evenly  flashing  the  programming  LED.  The 
flashing stops after 5 seconds.

 

 

Behavior after programming 

The  behavior  of  the  device  after  programming  with  the 
ETS  is  dependent  on  the  configuration.  The  description 
of the features, parameters and objects is in the applica
tion program description of the device. 
 
 

Note: 

When the programming key is pressed longer (> 0,5 s to 
2 s) no functions are activated. 
When the programming key is pressed longer (> 2 s) the 
device starts connection test. This is a special mode for 
Desigo TRA. The device may be blocked for the manufac
turer specific functions for approx. 10 seconds for the 
programming mode. This is indicated by briefly flashing 
the programming LED. 
 

 

 

Summary of Contents for UP 258D11 OPTISENS OFFICE

Page 1: ...ach functional block motion detector presence detector HVAC detector via corresponding parameters Each time a presence is detected the overshoot time is started Its duration is separately configurable for each functional block The end of presence is determined by the end of the overshoot time The duration of the dead time is also configurable per functional block It is used to protect the actuator...

Page 2: ... to control other devices The IR decoder can be controlled only with one of the Siemens IR remote controls shown in figure 1 The re mote controls have a range of 5 meters maximum The IR decoder cannot distinguish between remote con trols The functionality of button pairs A to F see dia gram in figure 1 will be configured via the ETS Figure 1 IR remote control units for UP 258D11 Commissioning Fact...

Page 3: ... Engineering Tool Software ETS version 3 0 f is required to load the application program Installation notes V V V V DANGER The device must be mounted and commissioned by an authorized electrician When connecting the device it should be ensured that the device can be isolated The device must not be opened For planning and construction of electric installations the relevant guidelines regulations an...

Page 4: ...ording to IEC 60664 1 III Bus safety extra low voltage SELV DC 24 V Device complies with EN 60669 2 1 EMC requirements Complies with EN 50428 Environmental conditions Climatic withstand capability EN 50090 2 2 Ambient operating temperature 5 45 C Storage temperature 20 70 C Relative humidity not condensing 5 to 93 Reliability Failure rate 410 fit at 40 C Markings KNX EIB CE mark In accordance with...

Page 5: ...g Basics The PIR sensor reacts to temperature differences The lower the temperature difference between the ambient temperature and the moving object the less sensitive the analysis In other words moving objects will not then be detected as efficiently and the catch ment area is restricted Note There must be an unobstructed line of sight to the person in the catchment area People behind walls etc i...

Page 6: ...ews E1 UP 258D device E2 Socket fixing screws E3 UP socket Depth min 40 mm 60 mm E4 Additional fixing holes offset by 90 Mounting the fixing clamps for mounting the device in suspended ceilings Extend the fixing claws slightly and push over the lugs on the UP 258D Figure 6 Mounting the fixing clamps for mounting the device in suspended ceilings G1 UP 258D device G2 Fixing clamp Installation in sus...

Page 7: ... protec tion for the tilting sensor head It can be removed before mounting the detector Separate the snaplock hooks on the shade with a screw driver and fold the shade down If you want to constrain the detection area you can cut out the shade The shade can be clipped back on if need after mounting the detector Figure 9 Mounting Dismounting the shade K1 UP 258D device K2 Shade K3 Screwdriver Cuttin...

Page 8: ... Ac cordingly be gentle while working Figure 12 Dismounting the design cover N1 UP 258D device N2 Design cover N3 Screwdriver caution Dimension drawing Dimensions in mm General notes The operating instructions must be handed over to the client Any faulty device is to be sent together with a return delivery note of the local Siemens office If you have further questions concerning the product please...