GAMMA

instabus

Technical Product-Information

February 2014

Temperature Controller

UP 237K

5WG1 237-2KB_1

UP 254K

5WG1 254-2KB_3

Technical-Manual

UP 237K, UP 254K, 5 pages

Siemens AG

Infrastructure & Cities Sector, Building Technologies

Update: http://www.siemens.com/gamma

ã

 Siemens AG 2014

Control Products and Systems

Subject to change without further notice.

P. O. Box 10 09 53, D-93009 Regensburg

2.8.2.8/2

Commissioning

For commissioning a control with the help of ETS (Engi-
neering Tool Software), the control together with the
suitable DELTA frame must first be inserted into a Bus
Transceiver Module (BTM) UP 117 which serves to sup-
ply power to the control and to transmit data via the KNX
Bus.
After removing the rotary knob for target value shifting,
the recess for the commissioning button and the com-
missioning LED of the control are visible.
Note: The bus transceiver module UP 117 and the asso-
ciated DELTA frame are not supplied and must be or-
dered separately.

With the help of ETS, the application program can be se-
lected, the specific parameter and addresses assigned
and transferred into the room temperature controls UP
237K and UP 254K.

Application program

The "0705 CO Room Temperature Control H+K 803002"
application program supports the following functions:

·

  Switching between automatic / manual operation and

switching the room operating mode with the button,

·

  Target value shifting or target value setting in °C with

the rotary knob,

·

  Status display with LEDs:

-

Displays (green) for manual operation and the cur-
rent room operating mode (comfort, pre-comfort,
energy-savings and protection mode),

-

Displays (red/yellow), whether the heating or cooling
valve is open,

-

Displays (red) for dew point alarm and open window.

·

 Room temperature control, adjustable as:

- heating only, cooling only, heating and cooling,
each selectable as
- heating with two-point control,
- heating with PI control,
- heating with PI control and sequence control
 (e.g. with floor and radiator heating),
- cooling with two-point control,
- cooling with PI control,
- cooling with PI control and sequence control.
   (e.g. with cooling ceiling and supply air cooler).

The following partial functions are part of room tempera-
ture control:

-

Room temperature measurement using the internal
temperature sensor with Offset setting,

-

Room temperature measurement using an external
temperature sensor with Offset setting,

-

Computation of current room temperature actual
value (internal and external sensors weighted),

-

With target value shifting: Basic target value as-
signment via parameter setting and/or via Bus,

-

With target value shifting: Computation of current
room temperature target value from basic target val-
ue and shifting,

-

time-restricted removal of night sinking or the pro-
tection mode (comfort prolongation),

-

with presence detection via the Bus, switching to the
"comfort" operating mode occurs,

-

Dew point mode can be activated via the Bus,

-

Evaluation of the window conditions via the Bus,

-

Frost protection / heat protection are reported via
the Bus,

-

PI control for heating / cooling with constant regulat-
ing variable-output (in %) or toggling regulating vari-
ables-output (on / off).

-

Separated or joint regulating variable output for
heating and cooling,

-

Separated regulating variable output for basic level
and auxiliary level for 2-level heating or cooling,

-

Switching the desired effect and scaling the regulat-
ing variable for heating/cooling is possible,

-

Maximal and minimal regulating variable for heat-
ing/cooling possible,

-

Operating condition (control status) can be read out
via the Bus,

Technical Data

Power supply

·

  via the flush-mounted bus transceiver module UP 117

Operating elements

·

  1 rotary button for manual adjustment of the setpoint

(control range and type of adjustment dependent on
the parameter setting and type of rotary button)

·

  1 button for toggling of the room operating mode and

vice versa

Display elements

·

  5 green LED`s for the current operating mode (com-

fort, pre-comfort, energy-saving, protection mode) and
for manual mode

·

  2 red LED`s for dew point alarm and open window

·

  2 red/yellow LED`s for Heating / cooling mode

Temperature measurement

·

  Measuring range: 0 ... + 40 °C

·

  Resolution: 0.08 K

·

  Accuracy of the sensor temperature:

±

 1.0 K under reference conditions,

±

 2.0 K under ambient conditions and in measuring

range

Connections

·

  10-pole plug-in connector  for connection with the bus

transceiver module UP 117

Summary of Contents for UP 237K

Page 1: ...utton Briefly pressing the button on the control causes switch ing in automatic mode the LED for the display of manual operation is not lit each time between comfort mode and pre comfort mode with four operating modes or between comfort mode and energy savings mode with three operating modes Moreover briefly pressing the button during active energy savings or protection mode starts a comfort prolo...

Page 2: ...ling ceiling and supply air cooler The following partial functions are part of room tempera ture control Room temperature measurement using the internal temperature sensor with Offset setting Room temperature measurement using an external temperature sensor with Offset setting Computation of current room temperature actual value internal and external sensors weighted With target value shifting Bas...

Page 3: ...mark In accordance with the EMV guideline residential and functional buildings low voltage guideline Location and function of the operating and display elements figure 1 Location of the operating and display elements A1 LED green illuminates during manual mode A2 LED green lights up continuously in comfort mode and blinks slowly in comfort prolongation A3 LED green illuminates during pre comfort m...

Page 4: ...h socket Υ WARNING The device must be mounted and commissioned by an authorised electrician The device may not be inserted in the same box as 230 V devices The device may be mounted in switch and socket combinations if VDE certified devices are used exclu sively The prevailing safety rules must be heeded The device may not be opened For planning and construction of electric installations the relev...

Page 5: ...8 5 Dismantling see figure 2 Remove rotary knob B1 or B2 Loosen screw B5 Remove controller together with DELTA frame Remove BTM UP 117 B8 according to dismantling in structions Dimension Drawing DELTA i system temperature controller UP 237K Dimensions in mm 55 55 16 DELTA style temperature controller UP 254K Dimensions in mm 68 68 20 General Notes The operating instructions must be handed over to ...