Siemens UH50 FLOW SENSOR Configuration Instructions Download Page 2

 
Ultraheat / Ultracold UH50 

Subject to change without prior notice 

UH 106-101k 

Page 2 / 15 

 

Meter for measurement of flow and energy in a heat or cold circuit with water using the ultrasonic 
principle. Important properties are:  
 

 

Non-wearing due to non-moving parts  

 

Measuring range of flow 1:100 according to EN 1434, 1:1000 total range 

 

Any mounting orientation, in flow or return, no setting sections or flow straighteners. 

 

Power measurement with maximum values, tariffs selectable 

 

Data logger for system monitoring 

 

60 monthly values

 

 

 

Logbook 

 

Battery or mains operated 

 

Optical interface according to EN 62056-21 

 

Big range of communication modules 

 

 

2 module slots for using 2 communication modules coincidental 

 

Also operable as a flow meter, cold or heat/cold meter 

 

Self-diagnostics 

 

Note: In the following text the term Meter covers the 
Heat  Meter  as  well  as  the  Cold  Meter  and  the  Flow 
Sensor if not mentioned otherwise. 

Safety information: 

  The meter is designed for circulating water of 

heating systems (not for drinking water!). 

  Do not pick up by the electronic unit 

  Be  careful  of  sharp  edges  (thread,  flange, 

measuring tube) 

  Installation and removal must be performed by 

qualified personnel only 

  Mounting  and  unmounting  are  only  permitted 

when the system is not under pressure 

  After  installation,  a  tightness  test  must  be 

conducted with cold pressure 

  Only  ever  use  under  service  conditions, 

otherwise dangers can arise and the warranty 
may be voided 

  Breaking the security seal voids the warranty 

  The  110 V / 230 V  versions  must  only  be 

connected by an electrician 

  The  lithium  batteries  must  be  properly 

returned 

  Lightning  protection  cannot  be  ensured;  this 

must be provided by the building wiring 

  Only  one  compartment  for  the  power  supply 

must  be  equipped  –  do  not  remove  the  red 
locking hatch 

General information

 

The  UH50  meter  is  used  for  energy  consumption 
metering  in  short  and  long-distance  district  heating 
and in apartment buildings. It is suitable both for cold 
metering  (alone  or  in  conjunction  with  metering 
quantities  of  thermal  energy)  or  for  pure  flowrate 
metering in water systems. 

 

Measuring accuracy 

Class 2 or 3 (EN 1434)  

Environment class 

A (EN 1434) for 

 

indoor installation 

Mechanical class 

M1  *) 

Electrical class 

E1  *) 

*) according 2004/22/EG EC directive 

Ambient humidity  

< 93% r. h. 

 

 

without condensation 

 

Electronic unit 

Storage temperature 

- 20 to 60°C 

Max. altitude 

2000 m above MSL 

Ambient temperature 

 5 to 55°C   

Housing degree of prot.   IP 54 per EN 60529 
Safety class 

 

  Line 110 / 230 V AC 

II per EN 61558 

  Line 24 V ACDC 

III per EN 61558 

Response threshold f. 

T 0.2 K 

Temperat. difference 

T  3 K to 120 K  

Temperat. meas. range  2...180°C 

 

Sensors 

Type 

Pt500 or Pt100 

 

per EN 60751 

Temperature range  

0...150°C  
(< 45 mm overall length) 
0...180°C 
(> 100 mm overall length) 

All volume measuring units 

(Consider the details on the meter) 

Mounting location 

return of flow  

Mounting orientation 

any 

Settling section 

none 

Metrological class  

1:100 

Temperature range 

5 to 130°C *) 

Recommended for… 
…heat application 

10 to 130°C 

…cooling application 

5 to 50°C 

*) national approvals may differ 

Maximum temperature 

150°C for 2000 h 

Maximum overload 

2.8 x q

p

 

Nominal pressure 

PN16

, PN25 

Summary of Contents for UH50 FLOW SENSOR

Page 1: ...prior notice UH 106 101k Page 1 15 Static Heat and Cold Meter UH50 issue January 2010 Configuration Instructions UH 106 101k Static meter for Heating and Cooling systems UH50 ULTRAHEAT UH50 ULTRACOLD UH50 FLOW SENSOR Version of firmware 5 15 and higher ...

Page 2: ...l voids the warranty The 110 V 230 V versions must only be connected by an electrician The lithium batteries must be properly returned Lightning protection cannot be ensured this must be provided by the building wiring Only one compartment for the power supply must be equipped do not remove the red locking hatch General information The UH50 meter is used for energy consumption metering in short an...

Page 3: ... 6 10 G 2 20 100 40 300 1 5 190 3 5 260 7 35 14 60 14 4 5 1 5 190 2 5 G 1 5 25 10 200 5 6 1 8 0 5 190 1 5 3 15 6 1 2 G 1 160 3 8 0 6 1 2 6 2 4 150 1 5 14 4 5 G 1 260 12 60 24 180 Tolerance pressure lost 5 Small meters qp 0 6 2 5 m h Overall length 110 mm thread Overall length 130 mm thread Overall length 190 mm thread Overall length 190 mm flange Large meters with threaded joint qp m h PN bar a b ...

Page 4: ... removable control cable may be separated during the installation When installation is done be sure that only paired parts volume part calculator are connected together Ball valve Example of mounting with a ball valve recommended up to DN25 Welded sleeve with pocket Example of mounting with pockets recommended above DN25 Mounting as a cold meter When mounting a cold meter or combined heat cold met...

Page 5: ...ction of service loops LOOP 1 n Service loop selection Service loop 1 Service loop 2 LOOP n Service loop n LCD button 1 advances the display to the next loop After the last loop the user loop LOOP 0 appears again LCD button 2 displays the content of the selected service loop Within a loop the LCD button 2 is used to advance to the next line of the display After the last line of the display the fir...

Page 6: ... flow temperature and return temperature with their date stamp for up to 60 months on the set day of each month Note The standard time used is Central European Time CET If daylight saving time is activated storage will be performed accordingly The monthly values can also be read out via the optical and the 20 mA interface Resolution of the display kWh MWh MJ GJ m Places after decimal point blinkin...

Page 7: ... rigid or flexible 0 2 2 5 mm flexible with end ferrules 0 25 1 5 mm conductor sizes 26 14 AWG Multiple conductor connection 2 conductors of same cross section rigid or flexible 0 2 0 75 mm flexible with end ferrules without plastic sleeve 0 25 0 34 mm flexible with TWIN ferrules with plastic sleeve 0 5 0 75 mm Recommended screwdriver 0 6 x 3 5 mm Tightening torque 0 4 Nm Permissible combinations ...

Page 8: ...d version A special version of the pulse module is available with an Opto MOS output Advantages low voltage drop and polarized bipolar Standard pulses Standard pulse significances kWh MJ m 10 15 25 40 2 5 3 5 60 Nom flowrate in m h 10 MJ 0 6 1 kWh 10 kWh 1 m 0 1 m 100 MJ 1 MJ depending on the unit for heat display Pulses for quantity of energy volume tariff register Period duration 200 ms Pulse du...

Page 9: ...The analog module converts a selectable measured value of the meter into an analog output signal 2 output signals channel 1 channel 2 The following measured values can be selected power Flowrate Flow temperature Return temperature Temperature difference The following can be selected as the output signal 0 20 mA 4 20 mA 0 10 V Radio module Display on LCD RM radio module Please read the appropriate ...

Page 10: ...ature from the defined return temperature threshold instead of from the temperature difference Above return threshold T1 is summated Below return threshold T2 is summated Display of the tariff situation on the LCD The current tariff status is shown in the user loop together with the quantity of energy or the volume No tariff status is shown for tariffs T7 and T8 for tariffs T2 T3 T4 T5 T6 T10 T11 ...

Page 11: ... 20 Monthly set day parameterized 21 Master reset performed 22 All times deleted 23 Missing time deleted 24 Event occurs Maxima deleted Read out is performed via the optical interface with the service software Data logger optional The data logger permits the archiving of data that the user can select from a predefined set of values The data logger contains four archives whose 8 channels can be ass...

Page 12: ... 5 m h length 110mm nominal pressure PN25 connection G B 22 Nominal flowrate 1 5 m h length 190mm nominal pressure PN16 connection G 1 B 23 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection flanged DN 20 24 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection G 1 B 25 Nominal flowrate 1 5 m h length 130mm nominal pressure PN16 connection G 1 26 Nominal flowra...

Page 13: ...r Pt500 removable mounting in the tube as an option G Sensor Pt500 removable mounted in the tube within a pocket H Sensor Pt100 not removable not mounted in the tube N Sensor Pt100 not removable mounted in the tube P Sensor Pt100 not removable mounting in the tube as an option R Sensor Pt100 not removable mounted in the tube within a pocket S Hardware dependent features 7 Sensor type Code Without ...

Page 14: ...GSM Module with 2 pulse inputs with battery SMS support WZU GM GPRS module with ext antenna magnetic attachment and UH50 power pack 110 230V cable 5m with interface for up to 8 M Bus meter to be read over GPRS amongst others Email support WZU GPRS Radio module WZU RM Radio module with external antenna WZU RM EXT For mounting of temperature sensors Code Adapter for ball valves to install temp eratu...