Supplied quantity of energy (tariff T7) 

In tariff register 1, a quantity of energy is summated 
that is calculated from the flow temperature (instead 
of from the temperature difference). 

Returned quantity of energy (tariff T8) 

In tariff register 1, a quantity of energy is summated 
that  is  calculated  from  the  return  temperature 
(instead of from the temperature difference). 

Heat/cold meter (tariff T9) 

In  tariff  register 1,  the  measured  quantity  of  cold;  in 
tariff  register 2,  the  measured  quantity  of  energy  is 
summated. In both cases a threshold can be defined 
via  the  flow  temperature  (“cold  threshold”,  “heat 
threshold”). 
Temperature 

above 

“heat 

threshold” 

and 

temperature difference > +0.2 K --> quantity of heat 
is acquired 
Temperature below “cold threshold” and temperature 
difference < -0.2 K --> quantity of cold is acquired 

Tariff control via timer switch (tariff T10) 

For tariff control, one switch-off time and one switch-
on  time  per  day  can  be  defined.  At  the  switch-on 
time, summation of the quantity of energy or volume 
is  started  in tariff register 1; at the switch-off time, it 
is ended. 

Tariff control via M-bus (tariff T11) 

In  tariff  registers  1,  2  and  3,  either  the  quantity  of 
energy  or  the  volume  can  be  summated.  With  the 
relevant M-bus command, one of the 3 tariffs can be 
activated or all tariffs can be deactivated. 

Surcharge  quantity  tariff  by  means  of  return 
temperature (tariff T12) 

The  quantity  of  energy  is  summated  depending  on 
the return temperature in tariff registers 1 or 2. 
The summated quantity of energy is calculated from 
the  difference  of  the  return  temperature  from  the 
defined  return  temperature  threshold  (instead  of 
from the temperature difference). 
Above return threshold: T1 is summated 
Below return threshold: T2 is summated 

Display of the tariff situation on the LCD 

The  current  tariff  status  is  shown  in  the  user  loop 
together with the quantity of energy or the volume. 
No tariff status is shown for tariffs T7 and T8. 

for tariffs T2, T3, T4, T5, T6, T10, T11 and T12 

 

no tariff register active 

  tariff register 1 active 

  tariff register 2 active 

  tariff register 3 active 

for tariff T9 (cold/heat meter) 

  no tariff register active 

  tariff register 1 active 

  tariff register 2 active 

The type of tariff and the associated parameters are 
displayed in service loop LOOP 4. 

 

for T2, T3, T4, T5, T6 
at intervals of 2s with threshold value 1/2/3 

  for T7 

  for T8 

 

for T9; 
at intervals of 2s 

for T10; 
switching times at intervals of 2s 

 

  for T11 

  for T12 

The  contents  of  the  tariff  registers  are  displayed  in 
the user loop after the quantity of energy. 

for tariffs T2, T3, T4, T5, T6, T10, T11 and T12 

 

tariff register 1 

  tariff register 2 

  tariff register 3 (not for T12) 

 

 

  for tariff T7 

  for tariff T8 

 

for tariff T9 

 

Error messages 

The  meter  constantly  performs  self-diagnostics  and 
can display various error messages. 
Error  

Error / action to be taken: 

 

code:

 

F0 

No flow; 
air in measuring unit / pipe, vent pipe 

F1 

Interruption of flow sensor  

F2 

Interruption of return sensor 

F3 

Electronic for temperature evaluation defective 

F4 

Battery empty; replace! 

F5 

Short circuit flow sensor 

F6 

Short circuit return sensor 

F7 

Fault in the internal memory 

F8 

F1, F2, F3, F5 or F6 pending for longer than 8 hours. 
No more measurements are performed. 

F9 

Error in the electronics 

Message  F8  has  to  be  reset  in  parameter  setting 
mode  (manually  or  service  software).  All  other  error 
messages  are  cleared  automatically  once  the  error 
has been corrected. 
 

Summary of Contents for UH50 FLOW SENSOR

Page 1: ...prior notice UH 106 101k Page 1 15 Static Heat and Cold Meter UH50 issue January 2010 Configuration Instructions UH 106 101k Static meter for Heating and Cooling systems UH50 ULTRAHEAT UH50 ULTRACOLD UH50 FLOW SENSOR Version of firmware 5 15 and higher ...

Page 2: ...l voids the warranty The 110 V 230 V versions must only be connected by an electrician The lithium batteries must be properly returned Lightning protection cannot be ensured this must be provided by the building wiring Only one compartment for the power supply must be equipped do not remove the red locking hatch General information The UH50 meter is used for energy consumption metering in short an...

Page 3: ... 6 10 G 2 20 100 40 300 1 5 190 3 5 260 7 35 14 60 14 4 5 1 5 190 2 5 G 1 5 25 10 200 5 6 1 8 0 5 190 1 5 3 15 6 1 2 G 1 160 3 8 0 6 1 2 6 2 4 150 1 5 14 4 5 G 1 260 12 60 24 180 Tolerance pressure lost 5 Small meters qp 0 6 2 5 m h Overall length 110 mm thread Overall length 130 mm thread Overall length 190 mm thread Overall length 190 mm flange Large meters with threaded joint qp m h PN bar a b ...

Page 4: ... removable control cable may be separated during the installation When installation is done be sure that only paired parts volume part calculator are connected together Ball valve Example of mounting with a ball valve recommended up to DN25 Welded sleeve with pocket Example of mounting with pockets recommended above DN25 Mounting as a cold meter When mounting a cold meter or combined heat cold met...

Page 5: ...ction of service loops LOOP 1 n Service loop selection Service loop 1 Service loop 2 LOOP n Service loop n LCD button 1 advances the display to the next loop After the last loop the user loop LOOP 0 appears again LCD button 2 displays the content of the selected service loop Within a loop the LCD button 2 is used to advance to the next line of the display After the last line of the display the fir...

Page 6: ... flow temperature and return temperature with their date stamp for up to 60 months on the set day of each month Note The standard time used is Central European Time CET If daylight saving time is activated storage will be performed accordingly The monthly values can also be read out via the optical and the 20 mA interface Resolution of the display kWh MWh MJ GJ m Places after decimal point blinkin...

Page 7: ... rigid or flexible 0 2 2 5 mm flexible with end ferrules 0 25 1 5 mm conductor sizes 26 14 AWG Multiple conductor connection 2 conductors of same cross section rigid or flexible 0 2 0 75 mm flexible with end ferrules without plastic sleeve 0 25 0 34 mm flexible with TWIN ferrules with plastic sleeve 0 5 0 75 mm Recommended screwdriver 0 6 x 3 5 mm Tightening torque 0 4 Nm Permissible combinations ...

Page 8: ...d version A special version of the pulse module is available with an Opto MOS output Advantages low voltage drop and polarized bipolar Standard pulses Standard pulse significances kWh MJ m 10 15 25 40 2 5 3 5 60 Nom flowrate in m h 10 MJ 0 6 1 kWh 10 kWh 1 m 0 1 m 100 MJ 1 MJ depending on the unit for heat display Pulses for quantity of energy volume tariff register Period duration 200 ms Pulse du...

Page 9: ...The analog module converts a selectable measured value of the meter into an analog output signal 2 output signals channel 1 channel 2 The following measured values can be selected power Flowrate Flow temperature Return temperature Temperature difference The following can be selected as the output signal 0 20 mA 4 20 mA 0 10 V Radio module Display on LCD RM radio module Please read the appropriate ...

Page 10: ...ature from the defined return temperature threshold instead of from the temperature difference Above return threshold T1 is summated Below return threshold T2 is summated Display of the tariff situation on the LCD The current tariff status is shown in the user loop together with the quantity of energy or the volume No tariff status is shown for tariffs T7 and T8 for tariffs T2 T3 T4 T5 T6 T10 T11 ...

Page 11: ... 20 Monthly set day parameterized 21 Master reset performed 22 All times deleted 23 Missing time deleted 24 Event occurs Maxima deleted Read out is performed via the optical interface with the service software Data logger optional The data logger permits the archiving of data that the user can select from a predefined set of values The data logger contains four archives whose 8 channels can be ass...

Page 12: ... 5 m h length 110mm nominal pressure PN25 connection G B 22 Nominal flowrate 1 5 m h length 190mm nominal pressure PN16 connection G 1 B 23 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection flanged DN 20 24 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection G 1 B 25 Nominal flowrate 1 5 m h length 130mm nominal pressure PN16 connection G 1 26 Nominal flowra...

Page 13: ...r Pt500 removable mounting in the tube as an option G Sensor Pt500 removable mounted in the tube within a pocket H Sensor Pt100 not removable not mounted in the tube N Sensor Pt100 not removable mounted in the tube P Sensor Pt100 not removable mounting in the tube as an option R Sensor Pt100 not removable mounted in the tube within a pocket S Hardware dependent features 7 Sensor type Code Without ...

Page 14: ...GSM Module with 2 pulse inputs with battery SMS support WZU GM GPRS module with ext antenna magnetic attachment and UH50 power pack 110 230V cable 5m with interface for up to 8 M Bus meter to be read over GPRS amongst others Email support WZU GPRS Radio module WZU RM Radio module with external antenna WZU RM EXT For mounting of temperature sensors Code Adapter for ball valves to install temp eratu...

Page 15: ...Ultraheat Ultracold UH50 Configuration Instructions UH 106 101k Page 15 15 ...

Reviews: