background image

1.

2.

3.

4.

5.

6.

7.

8.

9.
10.

Verify all power circuits are de-energized before making any
connections. The voltage rating of the device and system
must always be verified before energizing the TVSS. All
electrical connections should be performed by a qualified
(licensed) electrician.  All wiring must comply with the
National Electrical Code (NEC) and applicable local codes.

Maintenance of this Transient Voltage Surge Suppressor
should be performed by qualified electrical personnel
only.

During normal operation, hazardous voltages are
present inside the unit.

When servicing this unit, be sure to follow all electrical
safety precautions.

All power sources to this unit should be locked off
before servicing.  This will prevent the risk of receiving
an electrical shock.

Page 2

Installation

Installing the TPSA9040 TVSS:

To install the TVSS to the electrical panel equipment,
proceed as follows:

Ensure power to the electrical panel equipment has
been disconnected.
Remove the screws securing the outer panel equipment
cover to the electrical panel equipment (see Figure 1).
Select the location where the TVSS will be mounted
(should be based on the internal configuration of the
electrical panel equipment and the physical surround-
ings outside the equipment).  Note that the TVSS’s lead
length must be minimized to achieve maximum
performance.  Once the location has been determined,
drill or punch a 7/8” diameter hole in the top, bottom or
side surface of the electrical panel equipment.  The ideal
mounting location will also allow the TVSS to be secured
to the wall or panel in addition to using the chase nipple.
Screw one of the conduit nuts on to the chase nipple
until it bottoms out.  Note: bonding of the conduit
connections to the electrical panel equipment is not
automatic, and must be provided as part of the installa-
tion (remove paint from the electrical panel equipment
surface prior to installing the TVSS and  chase nipple).
Push the leads from the TVSS through the 7/8” diameter
hole toward the inside of the electrical panel equip-
ment. Push the leading part of the chase nipple through
the hole and secure the TVSS using a second conduit
nut (sandwiching the metal wall of the electrical panel
equipment between the two conduit nuts).
If possible, to provide extra rigidity in the installation,
attach the TVSS to the wall or electrical panel equip-
ment using installer supplied hardware.
Trim the leads from the TVSS as short as possible, but
still allowing the following connections to be made (see
Figure 2):

Black wires ( two in number ) go to the nearest
free 20 amp circuit breaker. The phase of each
lead is marked with a white band and letter
designator (L1 & L2). Connect the TVSS leads
to the appropriate phases. (It is not critical which
black wire goes to the positions on the circuit
breaker, however connect to L1 and L2 if known.)

Connect the white Neutral wire to the neutral bar
using a set screw.

Connect the green Ground wire to the electrical
panel equipment ground.

Note: Conducting dielectric and/or high potential testing
will cause internal damage to the TVSS unit. DO NOT
perform dielectric or high potential tests with the phase
or neutral TVSS wires connected.

Install the panel equipment cover.
Apply power to the panel equipment. LEDs will illumi-
nate on the TVSS.  If any connected phase LED on the
TVSS does not illuminate, remove power, check all

Hazardous voltage.

Will cause death or serious injury.

Disconnect power before

working on this equipment

!!!!!

 DANGER

HAZARDOUS VOLTAGE

BONDING BETWEEN CONDUIT CONNECTIONS

IS NOT

 AUTOMATIC AND MUST BE PROVIDED

AS PART OF THE INSTALLATION.

DO NOT CONDUCT DIELECTRIC AND/OR HIGH

POTENTIAL TESTING ON THIS UNIT.

THIS TESTING WILL CAUSE INTERNAL DAMAGE

CAUTION

!!!!!

Summary of Contents for TPSA9040

Page 1: ...s TPSA9040 Residential Transient Voltage Surge Suppressor User s Manual ...

Page 2: ...trical distribution equipment capable of delivering not more than 25 000 rms symmetrical amperes During installation into an electrical system the TPSA9040 must NOT be energized until the electrical system is installed inspected and tested All conductors must be connected and functional including neutral if required Failure to follow the guidelines in this manual can lead to abnormally high voltag...

Page 3: ... not automatic and must be provided as part of the installa tion remove paint from the electrical panel equipment surface prior to installing the TVSS and chase nipple Push the leads from the TVSS through the 7 8 diameter hole toward the inside of the electrical panel equip ment Push the leading part of the chase nipple through the hole and secure the TVSS using a second conduit nut sandwiching th...

Page 4: ... k n i l B s d n u o S t i n U e c a l p e R G G s k n i l B s d n u o S d n u o r G o t l a r t u e N k c e h C t i n U g n i c a l p e R e r o f e b n o i t c e n n o C connections and test again If any connected phase LED still does not illuminate contact Siemens Technical Support at 1 888 333 3545 The TPSA9040 is equipped with an audible alarm which will sound in the event of an alarm conditio...

Page 5: ... e s n o p s e R e g a t l o V h g u o r h T t e L d n o c e s o n a n 1 e r i w f o m c 7 1 3 t o o f 1 o r c i m 0 2 8 A k 3 V k 6 t o o f r e p s t l o v 5 7 1 e g a t l o v p m a l c e h t o t d e d d a e r a s d n o c e s e z i S e r i W G W A 2 1 e z i S e r i W g n i t a r e u q r o t r o f r e k a e r B t i u c r i C e e S d n a r e k a e r B t i u c r i C e u q r o T n o i t a l l a t s n...

Page 6: ... electronic devices including but not limited to microwave ovens audio and stereo components satellite dish equipment video equipment televisions computers or fax machines Siemens total aggregate liability under this Additional Limited Warranty shall be the lesser of 20 000 or the deductible amount of any applicable insurance policy covering such connected Major Household Appliance This Additional...

Page 7: ...4 ext 1234 www sea siemens com surge 2004 Siemens Energy Automation Inc All Rights Reserved Siemens is a registered trademark of Siemens AG Product names mentioned may be trademarks or registered trademarks of their respective companies Specifications are subject to change without notice Order PBOM 051704 New 2 5M100DW ...

Reviews: