background image

Description

Ratings

Service Voltage (3-Phase) 240 VAC Delta OR 120/208 VAC Wye
Short Circuit Current 

Rating (SCCR)

200 kA

Nominal Discharge 

Current (In)

20 kA

SPD Type

Type 1 (Can also be used in Type 2 applications)

Surge Protection 

Technology

TFMOV

Protection Mode

3 for Delta configuration

6 for Wye configuration (neutral tied to ground)

VPR (Vpk)

VOLTS (V) 

MODE 

VPR (Vpk)

240  L-L 1200

208/120 L-L  1200

 

L-N 700

Maximum Continuous 

Operation Voltage (MCOV)

L-L: 300 VAC

L-N: (for Wye configuration only): 150 VAC

Input Power Frequency

50/60Hz

Diagnostics

Green LED indicates surge protection present

Enclosure Rating

NEMA/Type 4X water tight plastic enclosure for 

outdoor and indoor installation

Installation Point

Electrical panel/disconnect

Dimensions

4.3” X 4.1” X 2.3”

Operating Temperature

-40°F to 185°F (-40°C to 85°C)

Operating Humidity

Less than 85%, noncondensing

Operating Altitude

Less than 2000 meters

Agency Certification and 

Approvals

ANSI/UL1449 4th Edition Listed Device - cULus 

Listed

The ICM530 is a UL Listed Type 1&2 Surge Protective Device for three phase 

Delta 240 VAC or Wye 120/208 VAC three phase voltage configurations. 

When a surge occurs, the ICM530 will absorb the surge up to the limits 

expressed in the specifications section of this guide. The ICM530 

incorporates thermal protection on the surge elements (TMOV’s) which 

allows for safe disabling of the surge elements when a surge exceeds the 

thermal limits of the device. The ICM530 has a status light on the control 

which identifies operational status when illuminated. The ICM530 can 

be installed as a Type 1 or Type 2 device for both indoor and outdoor 

applications. Suitable for use on a circuit capable of delivering not more 

than 200kA RMS symmetrical amperes, 240V maximum (Convient à des 

circuits produisant au plus 200kA RMS A eff.”, 240V maximum).

Periodically check the LED status on the SPD. If the Greenlight is OFF, 

the protection is no longer available and the SPD needs to be replaced 

immediately. 12 AWG stranded copper wire or larger required. Product 

contains no serviceable parts. This device features an internal protection 

that will disconnect the surge protective component at the end of its 

useful life but will maintain power to the load – now unprotected.

E347279

MAINTENANCE

MODE OF OPERATION

SPECIFICATIONS

The conductors used to connect the SPD shall not be any longer 
than necessary and shall avoid unnecessary bends.
1. Turn off the main breaker and/or main power to the service 

disconnect.

2. Determine if you have a Wye or Delta configuration.
3. Verify your mains voltage and match that with ICM530 ratings.
4. Remove the cover on service disconnect or the electrical panel.
5. Mount the ICM530 through the 3/4” conduit connection of the 

electrical panel.

6. Remove the retaining ring and washer on the ICM530.
7. Feed the wires into the electrical panel or service disconnect.
8. Re-secure the retaining ring and washer.
9. Route the white wire to the neutral lug and secure.

Wiring Type 1 installation

•  Route the three black wires to the appropriate L1, L2, L3 connections  

before the breaker panel as seen in the wiring diagram for Type 1 
installation and according to your local, state, and national electrical 
codes.

•  There will be a white wire which is only used in the Wye configuration 

and which needs to be capped off in the Delta configuration.

Wiring Type 2 installation 

•  Route and connect the three black wires (L1, L2, and L3) to the 

individual breakers on the circuit breaker panel as seen in the wiring 
diagram for Type 2 installation and according to your local, state and 
national electrical codes.

•  There will be a white wire which is only used in the Wye configuration 

and which needs to be capped off in the Delta configuration.

10. Reinstall cover on service disconnect or the electrical panel.

11. Restore power; Green LED should be on indicating full protection.

ELECTRICAL SHOCK HAZARD!

 – Before installing 

this unit, turn off power at the main service panel by 

removing the fuse or switching the appropriate circuit 

breaker to the OFF position.

•  WARNING — No Serviceable Parts  (Attention: Aucune pièce 

remplaçable ou reparable).

• WARNING — Shock hazard — 

Do not open (ATTENTION – RISQUE 

DE CHOC – NE PAS OUVRIR).

INSTALLATION, OPERATION & APPLICATION GUIDE

For more information on our complete range of American-made products – plus wiring 

diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com

ICM530

Surge Protective Device for 3-Phase Delta 240 VAC or Wye 120/208 VAC

IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS

Limited lifetime 

product, up to a 3-year 

$10,000 connected 

equipment warranty

Please follow all State, Local and National electrical codes when 

installing this product. Installation should only be done by a licensed 

electrician for Type 1 devices or a licensed HVAC technician for Type 

2 devices.