Table 4:  CONTENTS for installation in 400/600 amp S1/S2 and All 

SE Panels

Item Description

Qty.

1

TPS3 (See Page 2, Table 1)

1

2

1/4-20 Hex Head SEMS Assembly

3

3

10-24 Head Thread Forming Screw

6

4

TPS3 Neutral Connection Point

-

5

TPS3 Mounting Bracket 

1

6

Phase Connectors

3

7

1/4" Carriage Bolt

3

8

1/4" Belleville Washer Nut

3

Determine  the  mounting  location  of  the  TPS3  in  the  distribution 
equipment. If it is to be mounted in the top of the distribution equipment 
or relocated after installation, internal phase labeling connections 
must be changed to ensure proper diagnostic board indication. 

TPS3 01 Installation Instructions for: 400/600 amp S1/S2 and All SE Panels

If model number includes W option suffix, additional instructions follow

Note that this installation is very similar to TPS3 used in S3 Panels 
except that the neutral connector is wired rather than pigtailed 
and the neutral connector is at line end of the panel.

The following instructions are for the installation of Siemens TPS3 
01 and L1 SPD modules in Siemens 400/600 amp S1/S2 and all SE 
Panels.  All hardware is supplied for complete installation of the TPS3 
module.

Figure 4:  400/600 AMP S1/S2 AND ALL SE PANELS - TPS3 01 Unit  

with the NK Accessory Kit

These modifications should be made prior to installation. If the TPS3 
module is field installed in the bottom, or if it is mounted in a factory 
assembled  panelboard,  the  internal  phase  label  connections  are 
correct as shipped.  

Internal Phase Labeling Connections
A single 14 wire ribbon cable is attached to the display pcb.   
When the ABC phase sequence changes to CBA, the single connector is 
removed from the normal “ABC” jack and installed in the jack labeled 
“CBA”

Lock off all power supplying this equipment before working on it.  
Remove the trim and dead front. 

Install  the  mounting  bracket  (Item  5)  to  the  base  rail  as  shown 
in  Figure  3  using  two  (2)  of  the  #10  thread  forming  screws  
(item 3).

Position the TPS3 unit on the panel base rail so that the phase tabs 
are on top of the interior bus and the four mounting holes line up 
with the two holes in the base rail and the two holes in the mounting 
bracket.

Attach the TPS3 unit (item 1) to the base rail using four (4) of the #10 
slotted hex washer head thread forming screws (item 3) provided as 
shown in Figure 3.

Fasten unit to the main bus using the phase connectors (item 6). The 
connectors will be attached to the unit with three (3) 1/4" hex head 
SEMS assemblies (item 2) provided. Then they will be connected to 
the interior with three (3) 1/4" carriage bolts and three (3) belleville 
washer nuts (items 7 & 8).  Do not tighten at this time.

Fasten TPS3 neutral to panel neutral at the neutral connection point 
(item 4).

Torque all connections to the values as specified on the installation and 
maintenance instruction label affixed to the rear of the dead front.

Replace deadfront and trim.

CONDUCTING DIELECTRIC AND/OR 

HI-POTENTIAL TESTING WILL CAUSE

INTERNAL DAMAGE TO TPS3 UNIT.

Do not perform dielectric or high potential 

tests with the TPS3 unit installed.

CAUTION

V

Hazardous voltage.

Will cause death or serious injury.

Keep Out.

Qualified personnel only.

Disconnect and lock off all power before 

working on this equipment.

V  

DANGER

6

Summary of Contents for TPS3

Page 1: ...User Manual USA TPS3 Internal Manual Surge Protective Device ...

Page 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Page 3: ...x 7 TPS3 05 and TPS3 06 Module Replacement Instructions 8 TPS3 01 and TPS3 06 Module Installation Instructions MCC 9 Operation 10 TPS3 Control and Diagnostic Display Panel 10 Display Panel with Surge Counter Option 10 Dry Contacts Feature 10 Maintenance 11 Troubleshooting Service 11 Abnormal N G Voltage Indicators 11 Module Replacement Service 11 Technical Support 12 Display Replacement 12 Prevent...

Page 4: ...ly hazardous situation which if not avoided could result in minor or moderate injury These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the pur...

Page 5: ...ect plug in type devices surge strips etc Theses devices are intended for installation 10 meters from the panel rationale based on IEEE Cat A location Type4 Surgesuppressioncomponents couldbeabasiccomponent or a complete module Type 4 components can be tested for Type 1 Type 2 or Type 3 applications 2008 NEC Art 285 UL 1449 3 SPD Types Types 1 2 3 4 Based on Location within electrical distribution...

Page 6: ...rnd Fig 4 K 380Y 220V 3Ø 4W Plus Grnd Fig 2 L 600Y 347V 3Ø 4W Plus Grnd Fig 2 S 400Y 230V 3Ø 4W Plus Grnd Fig 2 AVALABLE SURGE CURRENT RATING Surge Current Rating TPS3 01 TPS3 L1 TPS3 05 TPS3 L5 TPS3 06 TPS3 L6 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase AVAILABLE OPTIONS When Option is Not ...

Page 7: ...etc NEC and IEEE Std 142 2007 are appropriate standards For sensitive electronics and computer systems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolatin...

Page 8: ...n it Remove the trim and dead front Remove the two 2 deadfront supports Position the TPS3 unit on the panel base rail so that the TPS3 neutral connector is in front of the panel neutral and the phase tabs are behind the interior bus Slide the unit toward the interior until the four mounting holes line up with the four holes in the base rail Note IfaneutrallugismountedinthepositionwheretheTPS3neutr...

Page 9: ...A single 14 wire ribbon cable is attached to the display pcb WhentheABCphasesequencechangestoCBA thesingleconnectoris removed from the normal ABC jack and installed in the jack labeled CBA Lock off all power supplying this equipment before working on it Remove the trim and dead front Install the mounting bracket Item 5 to the base rail as shown in Figure 3 using two 2 of the 10 thread forming scre...

Page 10: ...ified for the purpose and conditions of use Additional instructions for TPS3 01 L1 SPDs including W option Suffix TheWoptionincludesrespositionedphaseconnectiontabsthatallow for wire connections to a circuit breaker within the panelboard This differs from non W models which bolts directly to bus bars The circuit breaker serves as a disconnector device and overcurrent protection to the connecting c...

Page 11: ...isonnect Lock off all power supplying this equipment before working on it Open unit door and turn the internal disconnect to the off position Remove the neutral lug wire from the disconnect switch Remove the phase wires from the TPS3 06 unit lugs Remove the TPS3 06 unit with the panel and diagnostics display and discard properly Replace units with the new TPS3 06 units Attach the phase lug wires t...

Page 12: ...on such that the display is visible to user and or protected via an access door A successful installation includes Meets all national and local codes Mount TPS as close as possible to electrical connection Ensure leads are as short and straight as possible Gently twist or tie wrap conductors together wherever possible Ensure that N G bonding hazard warning label is attached to TPS as reminder to i...

Page 13: ...verysuppression elementinthisSPDismonitored N Gsuppressionelementmonitoring is logic connected to Phase A Service LED red LED illuminates in the event of problems This indicator is logic connected to the Phase LEDs Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will sound Test Tests red Service LED and Audible Alarm and changes state of Dry Contacts Alarm Silence T...

Page 14: ...round It becomes an ungrounded system Please see previous section regarding SPDs on ungrounded systems Such systems are known to eventually produce abnormally high L G voltages SPDs will attempt to chase this system level overvoltage abnormality until the SPD fails This effect is accelerated on Wye systems where SPDs are designed for grounded systems SPDs for ungrounded systems generally have high...

Page 15: ...sealing gasket between the display and the enclosure is a key component ensuring weather resistance Replace the gasket whenever the display is removed Preventive Maintenance Inspection and Testing Inspection of the TPS3 SPD unit should be performed periodically to maintain reliable system performance and continued transient voltage surge protection The large variations in operating conditions enco...

Page 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 8 9 10 8171 ...

Reviews: