background image

General Information

This  device  features  internal  overcurrent  and  overtemperature 
protection that will disconnect affected surge suppression components 
at the end of their useful life, but will maintain power to the load – 
now unprotected.  If this situation is undesirable for the application, 
follow these instructions for servicing or replacing the device.

Service of this unit consists of replacing the internal module and/or 
display assembly.

There are no user-serviceable parts inside the replaceable module.  
Do not attempt to disassemble the module as it stores charge.

Precautionary Statement Regarding SPDs on Ungrounded Systems

Caution  –  Ungrounded  systems  are  inherently  unstable  and  can 
product excessively high line-to-ground voltages during certain fault 
conditions.  During these fault conditions, any electrical equipment 
including an SPD, may be subjected to voltages which exceed their 
designed ratings.  This information is being provided to the user so 
that an informed decision can be made before installing any electrical 
equipment on an ungrounded power system.

Overcurrent Protection

The TPS3 SPD unit draws very little current under normal operation and 
will only conduct currrent for a very brief duration upon encountering 
a transient surge. The TPS3 unit contains overcurrent and thermal 
protection to protect against abnormal overvoltage conditions.

System Grounding

An equipment grounding conductor must be used on all electrical 
circuits connected to the SPD. 

For the best performance, use a single point ground system where 
the service entrance grounding electrode system is connected to and 
bonded to building steel, metallic piping, driven rods, etc. (NEC and 
IEEE Std 142-2007 are appropriate standards). 

For sensitive electronics and computer systems, ground impedance 
should be as low as possible. When metallic raceway is used as an 
additional grounding conductor, an insulated grounding conductor 
should be run inside the raceway and sized per the NEC. Adequate 
electrical continuity must be maintained at all raceway connections. 
Do not use isolating bushings to interrupt a metallic raceway run. 

A separate isolated ground for the SPD is NOT recommended because 
it  may  isolate  the  SPD  from  the  rest  of  the  electrical  system,  thus 
decreasing performance. Proper equipment connections to grounding 
system and ground grid continuity should be verified via inspections 
and tested on a regular basis as part of a comprehensive electrical 
maintenance program.

On 4-Wire Power Systems, neutral to ground bonding (Main Bonding 
Jumper) must be installed per the NEC

®

.  Failure to do so WILL damage 

SPDs.

Environment

The unit is designed to operate inside the equipment in a room ambient 
temperature range of: -40

o

 C (-40

o

 F) to +60

o

 C (+140

o

 F) with relative 

humidity of 0%-95% (non-condensing).

Audible Noise

The SPD’s background noise is negligible which permits installation 
within the equipment in almost any room.

Dead  front  modification  Instruction  Changes  for  P1  SPD 
Instructions

The  TPS3  unit  requires  a  dead  front  opening  to  display  its  face 
plate.  Remove any installed cover from a dead front opening at the 
TPS3 module location. If there is no dead front opening, follow the 
instructions in Fig. 2 to create an opening by removing a knockout 
plate.

P1 Dead Front Knockout Plate Removal Instructions

Stand the removed dead front on the floor with the plate to be removed 
in the upper position, as shown below. Grasping the upper edge of 
the dead front, press the cover plate out of the cutout. 

Figure 2:  Dead Front Modification Instruction

4

Summary of Contents for TPS3

Page 1: ...User Manual USA TPS3 Internal Manual Surge Protective Device ...

Page 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Page 3: ...x 7 TPS3 05 and TPS3 06 Module Replacement Instructions 8 TPS3 01 and TPS3 06 Module Installation Instructions MCC 9 Operation 10 TPS3 Control and Diagnostic Display Panel 10 Display Panel with Surge Counter Option 10 Dry Contacts Feature 10 Maintenance 11 Troubleshooting Service 11 Abnormal N G Voltage Indicators 11 Module Replacement Service 11 Technical Support 12 Display Replacement 12 Prevent...

Page 4: ...ly hazardous situation which if not avoided could result in minor or moderate injury These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the pur...

Page 5: ...ect plug in type devices surge strips etc Theses devices are intended for installation 10 meters from the panel rationale based on IEEE Cat A location Type4 Surgesuppressioncomponents couldbeabasiccomponent or a complete module Type 4 components can be tested for Type 1 Type 2 or Type 3 applications 2008 NEC Art 285 UL 1449 3 SPD Types Types 1 2 3 4 Based on Location within electrical distribution...

Page 6: ...rnd Fig 4 K 380Y 220V 3Ø 4W Plus Grnd Fig 2 L 600Y 347V 3Ø 4W Plus Grnd Fig 2 S 400Y 230V 3Ø 4W Plus Grnd Fig 2 AVALABLE SURGE CURRENT RATING Surge Current Rating TPS3 01 TPS3 L1 TPS3 05 TPS3 L5 TPS3 06 TPS3 L6 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase AVAILABLE OPTIONS When Option is Not ...

Page 7: ...etc NEC and IEEE Std 142 2007 are appropriate standards For sensitive electronics and computer systems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolatin...

Page 8: ...n it Remove the trim and dead front Remove the two 2 deadfront supports Position the TPS3 unit on the panel base rail so that the TPS3 neutral connector is in front of the panel neutral and the phase tabs are behind the interior bus Slide the unit toward the interior until the four mounting holes line up with the four holes in the base rail Note IfaneutrallugismountedinthepositionwheretheTPS3neutr...

Page 9: ...A single 14 wire ribbon cable is attached to the display pcb WhentheABCphasesequencechangestoCBA thesingleconnectoris removed from the normal ABC jack and installed in the jack labeled CBA Lock off all power supplying this equipment before working on it Remove the trim and dead front Install the mounting bracket Item 5 to the base rail as shown in Figure 3 using two 2 of the 10 thread forming scre...

Page 10: ...ified for the purpose and conditions of use Additional instructions for TPS3 01 L1 SPDs including W option Suffix TheWoptionincludesrespositionedphaseconnectiontabsthatallow for wire connections to a circuit breaker within the panelboard This differs from non W models which bolts directly to bus bars The circuit breaker serves as a disconnector device and overcurrent protection to the connecting c...

Page 11: ...isonnect Lock off all power supplying this equipment before working on it Open unit door and turn the internal disconnect to the off position Remove the neutral lug wire from the disconnect switch Remove the phase wires from the TPS3 06 unit lugs Remove the TPS3 06 unit with the panel and diagnostics display and discard properly Replace units with the new TPS3 06 units Attach the phase lug wires t...

Page 12: ...on such that the display is visible to user and or protected via an access door A successful installation includes Meets all national and local codes Mount TPS as close as possible to electrical connection Ensure leads are as short and straight as possible Gently twist or tie wrap conductors together wherever possible Ensure that N G bonding hazard warning label is attached to TPS as reminder to i...

Page 13: ...verysuppression elementinthisSPDismonitored N Gsuppressionelementmonitoring is logic connected to Phase A Service LED red LED illuminates in the event of problems This indicator is logic connected to the Phase LEDs Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will sound Test Tests red Service LED and Audible Alarm and changes state of Dry Contacts Alarm Silence T...

Page 14: ...round It becomes an ungrounded system Please see previous section regarding SPDs on ungrounded systems Such systems are known to eventually produce abnormally high L G voltages SPDs will attempt to chase this system level overvoltage abnormality until the SPD fails This effect is accelerated on Wye systems where SPDs are designed for grounded systems SPDs for ungrounded systems generally have high...

Page 15: ...sealing gasket between the display and the enclosure is a key component ensuring weather resistance Replace the gasket whenever the display is removed Preventive Maintenance Inspection and Testing Inspection of the TPS3 SPD unit should be performed periodically to maintain reliable system performance and continued transient voltage surge protection The large variations in operating conditions enco...

Page 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 8 9 10 8171 ...

Reviews: