background image

Introduction

Thank  you  for  choosing  a  Siemens  TPS3  09  Surge  Protective 
Device (SPD). It is a high quality, high energy surge suppressor 
designed  to  protect  sensitive  equipment  from  damaging 
transient overvoltages. TPS3 09 is parallel connected such that 
circuit ampacity is unlimited. Proper installation is important to 
maximize performance. Please follow steps outlined herein. This 
entire Operation and Maintenance Manual should be read prior 
to beginning installation. These instructions are not intended to 
replace  national  or  local  codes.  Follow  all  applicable  electrical 
codes to ensure compliance. Installation of this SPD should only 
be performed by qualified electrical personnel. 

Siemens SPDs are extensively tested in accordance with industry 
standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62, 
C62.72, UL1449, UL 1283, IEC 61643, CSA C22.2 No. 269, etc.

Industry Nomenclature Changes 

In the late 2000’s, there were significant nomenclature changes 
associated with a revision to UL 1449 and 2008 NEC® Article 285. 
TPS3 09 complies with the latest regulatory actions and is UL 1449 
& CSA 22.2 No. 269, Listed as such (VZCA.E321351). There is an 
emphasis on installation location, identified as Types 1, 2 and 3, 
outlined below.

Type 1 SPD:

 Installation on the line side or load side of the service 

disconnect overcurrent device. Type 1 SPDs may be used in Type 
2  installations.  Examples:  surge  arrestors,  lightning  arrestors, 
meter hubs, metering cabinets, ran out of breaker positions, etc.

Type  2  SPD:

  Downstream  of  service  disconnect;  probably  will 

connect  via  breaker.  Examples:  switchboards,  power  panels, 
panelboards, equipment, motors, pumps, etc. 

Type 3 SPD:

 Point of Use SPD, sometimes plug-connected SPD.

Type 4 SPD:

 Has different contexts in UL 1449 and CSA 22.2 No. 

269. Call for assistance. 

The TPS3 09s are available as Type 1 or Type 2 SPDs per UL 1449 
and CSA 22.2 No. 269. (Construction is identical for Type 1 and 
Type 2 Model 425s.) Type 1 SPDs are evaluated more rigorously 
by  UL  1449  for  NEC®  Article  285  and  CEC  compliance.  Type  1 
SPDs  and  their  connecting  leads  have  been  evaluated  for  line 
side  applications  without  need  for  supplemental  overcurrent 
protection. Type 1 SPDs include internal overcurrent protection. 
As a generalization, it is more practical to install SPDs on the load 
side of the main overcurrent protection device for maintenance 
and serviceability reasons. When connected on load side of main 
disconnect, we suggest connecting via a 30A circuit breaker due 
to 10 AWG conductors. The circuit breaker serves as a disconnect 
switch and provides NEC® imposed short circuit protection to the 
conductors in Type 2 applications. A change in the 2014 NEC® Ten 
Foot Tap Rule may be useful in certain applications: 240.21(B)(1)
(1)b Exception:

“When listed equipment, such as a surge protective 

devices(s)  [SPD(s)],  is  provided  with  specific  instructions 

on minimum conductor sizing, the ampacity of the tap 
conductors supplying that equipment shall be permitted to 
be determined based on the manufacturer’s instructions.”

TPS3  09  SPDs  have  demonstrated  200kA  Short  Circuit  Current 
Ratings (SCCR). 120V and 120/240V Model 425s have demonstrated 
100kA SCCRs. Confer to label on unit.
 

Simplified Explanation of Operation

SPDs sense overvoltage and create a momentary low impedance 
path to redirect harmful surge energy. They reset automatically 
and wait for the next surge. This is similar to the pressure relief 
valve on a water heater: pressure goes up, valve opens to relieve 
pressure and then resets. In an electrical system, an SPD senses 
overvoltage,  reduces  impedance  which  equalizes  damaging 
voltages  and  then  resets.  SPDs  are  capable  of  repeating  this 
function thousands of times.

•  Only qualified licensed electricians should install or service 

SPDs.

•  SPDs should never be installed or serviced when energized 

or during electrical storms.

•  Use  appropriate  safety  precautions  including  Personal 

Protection Equipment.

•  Failure  to  follow  these  instructions  can  result  in  death, 

serious injury, and/or equipment damage.

•  When used in outdoor applications, customer must seal the 

conduit nipple using watertight fittings (not included) to 
ensure a watertight connection.

•  Read this manual in entirety prior to installing.

WARNING

V

Hazardous Voltage & Shock Hazard

Figure 1:  SPD Types - NEC® Article 285 & UL 1449-4

SPD Types: Types 1, 2, & 3
Based on Location within electrical distribution system
(also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B & A)

1

Summary of Contents for TPS3 09 Series

Page 1: ...UL 1449 4th Edition SPD usa siemens com spd TPS3 09 User Manual USA ...

Page 2: ...age rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance wit...

Page 3: ...need for supplemental overcurrent protection Type 1 SPDs include internal overcurrent protection As a generalization it is more practical to install SPDs on the load side of the main overcurrent protection device for maintenance and serviceability reasons When connected on load side of main disconnect we suggest connecting via a 30A circuit breaker due to 10 AWG conductors The circuit breaker serv...

Page 4: ...ded systems are inherently unstable and can produce excessively high line to ground voltages during certain fault conditions During these fault conditions any electrical equipment including an SPD may be subjected to voltages which exceed their designed ratings This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an u...

Page 5: ...deenergized 5 Identify breaker location and SPD location Position SPD such that LEDs are best visible 6 Mount SPD weather resistant applications require additional sealing o rings etc not included Remove an appropriately sized knockout from panel Connect conductors as appropriate short and straight as possible Hi Legs are Phase B 7 Label or mark conductors as appropriate neutral white ground green...

Page 6: ...uch that on board LEDs are not readily visible A green LED bezel assembly includes two pre attached wires and two butt splice connectors The SPD includes two yellow 18 AWG wires pre wired through the SPD s nipple mounting connection Pre plan the installation per normal installation Instructions Mount the LED assembly in an appropriate conspicuous location Connect the LED wires to the yellow SPD wi...

Page 7: ...duct Returnedproducts mustbesenttothefactorywiththetransportationchargesprepaid In addition the company also warranties unlimited replacement of modular and component parts within the warranty period previously described Thecompanyspecificallydisclaimsallotherwarranties expressed or implied Additionally the company is not be responsible for incidental or consequential damages resulting from any de...

Page 8: ...tion provided in this manual contains merely general descriptions of characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the product An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract All product designations may be trademarks or produ...

Reviews: