Installation, connecting up, commissioning
3.2 Installation
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
43
WARNING
Substitution of components may impair suitability of the equipment.
3.2
Installation
WARNING
Open equipment
The device is "open equipment" acc. to the standard UL 61010-2-201. To fulfill
requirements for safe operation with regard to mechanical stability, flame retardation,
stability, and protection against contact, the following alternative types of installation are
specified:
•
Installation in a suitable cabinet.
•
Installation in a suitable enclosure.
•
Installation in a suitably equipped, enclosed control room.
WARNING
Cable temperatures
If the cable or housing socket exceeds 70 °C or the branching point of the cables exceeds
60 °C, special precautions must be taken. If the equipment is operated in an ambient
environment in excess of 40 °C, only use cables with permitted maximum operating
temperature of at least 80 °C.
NOTICE
Install and remove the TIM only when the power is off
Switch off the power supply of the TIM before you install or remove the TIM. Installing and
removing modules with the power supply on can lead to damage to the modules and to loss
of data.