background image

Installation Instructions

Document No. 129-102

March 6, 2018

Installation of TH 19X Thermostat in
TH 180 AP and TH 182 AP Aspirator
Wall Box

Item Number 129-102+4, Rev. BA

Page 1 of 3

Product Description

These instructions describe the recommended
method for replacing the thermostat in the
TH 180 AP or TH 182 AP Aspirating Wall Box
with a TH 19X Thermostat using the 192-648
Aspirator Adapter Kit. The TH 180 AP/TH 182
AP has only two air line connections; therefore,
1-pipe and 3-pipe devices should not be
installed in it.

Product Number

192-648

Warning/Caution Notations

WARNING

Personal injury or loss of life
may occur if you do not
perform a procedure as
specified.

CAUTION

Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.

Installation

Disassembly

NOTE:

   The numbers found in parentheses in

this procedure correspond to the
numbers shown in Figure 1. See
Table 1 for a parts list of the Aspirator
Adapter Kit.

1.  Remove and discard the old cover.

2.  Remove the two screws holding the old

thermostat in place and remove the
thermostat.

CAUTION:

Supply air will bleed out of the terminal
until the new thermostat is installed.

3.  Remove the five screws (5) holding the old

terminal plate (4) and gasket (2). Remove
the terminal plate and gasket. Discard the
gasket.

Table 1.  192-648 Aspirator Adapter Kit Parts List.

Item

Description

Quantity

1 Filter

1

2 Gasket

1

3 O-rings

2

4  Terminal 

plate

1

5  Screws 4-40 × 1/2-inch long

5

6  Screws 4-40 × 1-inch long

2

7  Tubing 

retainer

1

8  Aspirator 

nozzle

1

9  Aspirator 

plate

1

10  Seal gaskets

3

11 Cover

1

12  Cover screws 6/32 × 1-3/8 inch long

2

13  Spacer post

2

Assembly

NOTE:

   The numbers found in parentheses in

this procedure correspond to the
numbers shown in Figure 1. See
Table 1 for a parts list of the Aspirator
Adapter Kit.

1.  Replace the supply air filter (1) with the new

filter provided in the kit.

NOTE:

Be sure the gasket fits over the two
locator posts.

2.  Make sure the gasket surface is clean.

Place the new gasket (2) into the wall box.