TX-I/O Power Supply and Bus Modules
34
Siemens Industry, Inc.
TALON TX-I/O Modules and Island Bus Technical Reference
Bus Connection Module Product Diagram
1
2
3
4
5
6
CS
CD
T
CS
CD
TXIO0045R1
2
3
5
1
4
6
V
V
Bus Connection Module.
Bus Connection Module Features, Symbols, and Status LEDs
LED, Symbol, or Feature
Status
Indication
CS
-
24 Vdc Communication Supply for I/O modules and field
devices.
1
CD
-
Communication Data (Island bus signal).
2
TX-I/O bus connector (female)
-
Connection for the TC Modular, or left covered if at the
start of a TX-I/O bus. No field device supply.
ON
Normal operation. 24 Vac (supply voltage) input present;
fuse is intact.
3
Fuse LED for 24 Vac supply to field
devices
OFF
Error.
- No 24 Vac (supply voltage) input.
- Fuse is blown. (4A, 5 × 20 mm, 250V, medium-acting,
ceramic fuse)
-
Field device supply.
4
-
System neutral.
5
TX-I/O bus connector (male)
-
Connection for TX-I/O Modules. Includes field device
supply.
6
Fuse
-
4A fuse for field supply.
588-587
CONFIDENTIAL: For internal use only