Figure 2
SZE-4X Wiring Diagram
Figure 3
Smoke Detector and Shorting Type Device
Wiring Diagram
NOTES:
1. The SXL-EX Control Panel meets NFPA 72
Local requirements.
2. All field wiring must be in accordance with
NFPA 70, Article 760.
3.
Do not make any wiring connections
while the System is powered.
4. Form C relay contacts are shown de-
energized. They are not suitable for motor
or pilot duty.
5. Combined current output for NAC1, NAC2,
and auxiliary outputs is limited to 3.0 amps.
6. Equipment connected to these terminals
must be located within the same room.
7. In all cases the Siemens Industry, Inc.,
Model Number is the compatibility
identifier, including the Control Panel,
Module(s), and all Compatible Initiating
Devices.
4X
4X
Figure 4
PB-1191 Device Wiring Diagram
UL Listed EOL Device
3.9K, 1/2W, P/N 140-820386
(IDCs Supervised)
Class B (Style B)
UL Listed EOL Device
3.9K, 1/2W, P/N 140-820386
(IDCs Supervised)
Class B (Style B)
+ -
+ -
+ -
+ -
+ -
+ -
+ -
+ -
IDC 5
IDC 5
IDC 6
IDC 6
IDC 7
IDC 7
IDC 8
IDC 8
TB-3
TB-1
TB-2
To JP3
of SXL-EX
Main
Board
To JP3
of SXL-EX
Main
Board
JP1
FORM C
RELAY 1
FORM C
RELAY 1
(See
Note 6)
(See
Note 6)
(See Note 6)
(See Note 6)
(See
Note 6)
(See
Note 6)
(See
Note 6)
(See
Note 6)
(See
Note 6)
(See
Note 6)
FORM C
RELAY 2
FORM C
RELAY 2
FORM C
RELAY 3
FORM C
RELAY 3
FORM C
RELAY 4
FORM C
RELAY 4
OC 1 Programmable
OC 1 Programmable
External
Load
External
Load
External
Load
External
Load
External
Load
External
Load
External
Load
External
Load
To Ex24VDC
UL Listed, Regulated,
and Filtered power
supply.
To Ex24VDC
UL Listed, Regulated,
and Filtered power
supply.
To SXL-EX
Main Board
-V TB-3
To SXL-EX
Main Board
-V TB-3
If External
Power Supply
is not available,
connect to
SXL-EX Main
Board
+24V TB-3.
(See Note 5)
If External
Power Supply
is not available,
connect to
SXL-EX Main
Board
+24V TB-3.
(See Note 5)
See Open Collector Electrical Rating Table
and Note 6
See Open Collector Electrical Rating Table
and Note 6
+
-
SZE-4X
OC 2 Programmable
OC 2 Programmable
OC 3 Programmable
OC 3 Programmable
OC 4 Programmable
OC 4 Programmable
Programmable
Programmable
Programmable Programmable
See COMPATIBLE DETECTOR CHART and
INITIATING DEVICE CIRCUIT ELECTRICAL RATINGS
See COMPATIBLE DETECTOR CHART and
INITIATING DEVICE CIRCUIT ELECTRICAL RATINGS
Postive and Negative Ground Fault
Detected at <100K for Terminals on TB-3
Postive and Negative Ground Fault
Detected at <100K for Terminals on TB-3
PBA-1191 Device Wiring Diagram
TO
I
DC
Z
ONE
TO
I
DC
Z
ONE
-
-
-
-
+
+
+
+
EOL RES
I
STOR
4
.
7K, 1/4W, P/N 140-820188
EOL RES
I
STOR
4
.
7K, 1/4W, P/N 140-820188
PBA-1191
A
B
C
D
E
F
DO NOT
USE
DO NOT
USE
P/N 315-096018-8
INITIATING DEVICE CIRCUIT
Electrical Ratings
Voltage range: 18.2-26.8 VDC filtered
Supervisory current: 6mA
Alarm current: 120mA (max)
1. Maximum line impedance of 25 ohms
per IDC zone.
2. All IDC zones are supervised and power
limited per NFPA 70, Article 760.
3. Each IDC zone must use at least 18
AWG, 300V insulation, color-coded wire
for low voltage circuits where local
codes require conduit. Where local
codes permit, use limited energy
shielded cable rated at 300V.
4. Each IDC zone supports one initiating
device in alarm.
5. Maximum line capacitance is 10uF per
zone.
Figure 1
Mounting the SZE-4X Module
OPEN COLLECTOR
ELECTRICAL RATING TABLE
50mA (max) at 26.4 VDC (max)
Resistive Only
FORM C
RELAY ELECTRICAL RATINGS
2A at 30 VDC
200mA at 120 VAC Resistive Only